008
0015 – (High)
007/005
0015 – (Medium)
006
0015 – (Low)
LOW
MEDIUM
HIGH
6
CAUTION: Do not attempt to remove LED panel from circulator. Serious damage to circulator electronics may result.
ATTENTION: N'essayez pas de retirer le panneau de LED du circulateur. Des dommages sérieux à l'électronique du circu-
lateur peuvent en résulter.
0015e3 Performance Curves
Selection options are LOW, MEDIUM or HIGH. The 0015e3 circulator varies its speed in LOW and MEDIUM setting to maintain
a constant pressure differential (∆p-c) in the system as heating load increases or decreases. On HIGH setting, the 0015e3 runs
at full speed. See chart above for operating curves and equivalent 00 model at each setting.
O
r
a
n
g
e
L
E
D
6
. Programming your 0015e3 circulator:
Note: The 0015e3 is factory-programmed for MEDIUM setting. If this is your desired operating mode, no programming changes
are required.
To change operating settings:
Modify the performance of the circulator as needed by rotating the dial using a flat screwdriver. An orange LED will illuminate when
the circulator is powered on. The LED will flash each time a setting is changed. See diagram below to determine best setting for the
system.The selection of the right operating curve depends on the characteristics of the heating system and the actual heat demand.
See cross-reference replacement chart on page 8.
The 0015e3 has 3 Operating Settings:
• LOW - 5 feet of head constant pressure, variable speed.
• MEDIUM - 10 feet of head constant pressure, variable speed.
• HIGH - 18 feet of head max, full fixed speed.