0011-IFC Series Circulator Pump Brochure and Submittal

Submittal Data Information
Model 0011-IFC
®
Cartridge Circulator
Submittal Data # 101-084
Supersedes: 04/22/10
Effective: 06/10/13
Application
The 0011-IFC with an Integral Flow Check is designed to reduce installation costs
when zoning with 00
®
circulators. Typical uses include large residential or light
commercial high head / medium flow applications such as hydronic or radiant
heating, hydro-air fan coils, indirect water heaters or domestic water recirculation
systems. By locating the removable, spring-loaded IFC inside the pump casing,
a separate in-line flow check is eliminated. The reduced pressure drop of the IFC
increases the 0011 flow performance over in-line check valves. Both the IFC and
cartridge are easily accessed for service instead of replacing the entire unit.
Mounting Positions
Standard Optional OK if over 20 psi
Flange Orientation
Features
Integral Flow Check (IFC
®
)
Prevents gravity flow
Eliminates separate in-line flow check
Reduces installed cost, easy to service
Improved performance vs.
In-line flow checks
Unique replaceable cartridge
— Field serviceable
Unmatched reliability
— Maintenance free
Quiet, efficient operation
Direct drive-Low power consumption
Self lubricating, No mechanical seal
Standard high capacity output
— Compact design
Wide range of applications
Cast Iron or Stainless Steel construction,
Flanged connections
Materials of Construction
Casing (Volute): Cast Iron or Stainless Steel
Integral Flow Check:
Body, Plunger ..... Acetal
O-ring Seals ......... EPDM
Spring ...................... Stainless Steel
Stator Housing: ..............Aluminum
Cartridge: ...........................Stainless Steel
Impeller: .............................Non-Metallic
Shaft: ..................................... Ceramic
Bearings: ............................. Carbon
O-Ring & Gaskets: ......... EPDM
Model Nomenclature
F – Cast Iron, Flanged
SF – Stainless Steel, Flanged
IFC – Integral Flow Check
Performance Data
Max. Flow: 30 GPM
Max. Head: 31 Feet
Min. Fluid Temperature: 40˚F (4˚C)
Max. Fluid Temperature: 230°F (110˚C)
Max. Working Pressure: 125 psi
Connection Sizes:
3/4”, 1”, 1-1/4”, 1-1/2” Flange
FLOW-GPM
0246810 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
TOTAL HEAD-FEET
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
FLOW-M3/H
0.0 0.51.0 1.52.0 2.53.0 3.54.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0 9.510.0
TOTAL HEAD-METERS
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
009-IFC
0010-IFC
0011-IFC
0012-IFC
0013-IFC
0014-IFC
INTEGRAL FLOWCHECK (IFC
®
) MODELS
Electrical Data
Performance Field - 60Hz
Pump Dimensions & Weights
Taco Inc., 1160 Cranston Street. Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360
Taco (Canada) Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8 / (905) 564-9422 / Fax (905) 564-9436
www.taco-hvac.com
Low-Lead Compliant
Certifications & Listings
FOR INDOOR
USE ONLY
Models Casing
A B C D F G
Ship Wt.
in. mm in. mm in. mm in. mm in. mm in. mm lbs. Kg
0011-F4-2 IFC Cast Iron 7-1/2 191 6-1/8 156 3-1/2 89 3-5/16 84 5-1/2 140 6-1/2 165 12.0 5.5
0011-SF4-IFC St. Steel 7-1/2 191 6-1/8 156 3-1/2 89 3-5/16 84 5-1/2 140 6-1/2 165 12.0 5.5
Model Volts Hz Ph Amps RPM
HP
All Models
115
60 1 1.76 3250 1/8
Motor
Type
Permanent Split Capacitor
Impedance Protected
Motor
Options
220/50/1, 220/60/1, 230/60/1, 100/110/50/60/1