SR501-OR-4 Switching Relay Instruction Sheet (page 2)
Boiler Operation:
The  supply  water  temperature  from  a  boiler  can  be  controlled  by
cycling  the  boiler  on  and  off.  Modulation  of  the  boiler’s  operating
temperature  in  hot  water  heating  systems  not  only  provides  more
comfort  but  also  offers  significant  energy  savings.  The  cooler  the
boiler runs, the more efficient it is due to less heat losses up the flue
and reduced boiler jacket losses. 
Differential:
An on / off boiler must be operated with a differential in order to pre-
vent short cycling. When the supply water temperature drops below
the bottom rail of the differential, the boiler is turned on. The boiler is
then kept on until the supply water temperature rises above the top
rail of the differential. If the differential is too wide, there can be large
supply  water  temperature swings;  however,  if  the  differential is  too
narrow, the boiler short cycles and operates inefficiently. This control
can  be  set  for  two  different  boiler  differentials,  10°F  (6°C)  or  20°F
(12°C).  This  setting  will  help  to  achieve  an  appropriate  balance
between temperature swings and boiler efficiency. 
Minimum Boiler Supply:
Most boilers require a minimum supply water temperature in order to
prevent  corrosion  from  flue  gas  condensation.  The  control  should
therefore only modulate the boiler supply water temperature down to
the boiler manufacturer’s minimum recommended operating temper-
ature. Some boilers are designed to condense and should be oper-
ated at low  water  temperatures as much as  possible  for  maximum
efficiency.
SUPPLY WATER TEMPERATURE
TIME
Differential = 10°F (5°C
)
165
°F(74°C)
155°F (68°C
)
160°F (71°C
)
BOILER ON BOILER ON
BOILER OFF
BOILER OFF
OUTDOOR AIR TEMPERATURE
50
(10)
30
(-1)
10
(-12)
-10
(-23)
70
(21)
90
(32)
WWSD
T
EMPERATURE
°
F (
°
C)
SUPPLY WATER TEMPERATURE
110 (43)
70 (21)
90 (32)
210 (99)
170 (77)
150 (65)
130 (54)
190 (88)
RESET
RATIO
BOILER
MINIMUM
SEQUENCE OF OPERATION:
Powering Up the Control:
After the SR501-OR is powered up, the green power LED light will be on.
Heating Demand:
The SR501-OR receives a heating demand from thermostat or zone
control end switch closure on the R and W thermostat terminals. The
thermostat red LED light will also be turned on. The control can be
setup for boiler temperature reset or ON – OFF boiler operation.
Reset Demand:
When the SR501-OR receives a heating demand the controls enable
the boiler based on the reset cure. The Boiler Relay red LED light will
be turned on when the boiler relay is energized.
DHW Demand:
When the SR501-OR receives a  DHW  demand the controls enable
the boiler and ignore the boiler reset curve.  The DHW Override red
LED light will also be turned on.
Warm Weather Shut Down (WWSD):
When the outdoor temperature rises above 70°F (21°C), the control
turns off the boiler. This function only applies for space heating and
not DHW operation.
Boiler Operation:
When the SR501-OR has a reset demand, the system supply water
temperature is controlled by turning the boiler on and off. The control
calculates the target supply water temperature based on the outdoor
temperature, and the settings that were entered. The boiler operates
around a differential that is manually set by dip switch number 2. The
control includes a minimum on and off time for the boiler, in order to
minimize short cycling. 
Maximum Boiler Supply: 
The  SR501-OR  does  not  allow  the  boiler  target  temperature  to
exceed the boiler design temperature setting plus 10°F (6°C) up to a
maximum of 225°F (107°C). 
Minimum Boiler Supply: 
The SR501-OR has a 140°F minimum boiler setting which is used in
order to prevent corrosion from flue gas condensation. During mild
outdoor conditions, the boiler cycles around the minimum boiler set-
ting.  This  programmed  function  can  be  set  to  the  OFF  setting  for
condensing and electric boilers.
INSTALLATION:
Step One:
Check the contents of this package. If any of the contents listed are
missing  or  damaged,  please  contact  your  sales  representative  for
assistance.
The SR501-OR includes:
SR501-OR Boiler Reset Control and Switching Relay Combination
One Outdoor Sensor
One Strap on Sensor
Instruction Sheet
Replacement sensors are available from Taco, Inc.:
Strap on Sensor – 9300-2044RP
Outdoor Sensor – 9300-2052RP 
Note: Carefully read the details of the Sequence of Operation section
in this brochure to ensure that you have chosen the proper control for
your application.
CAUTION: Improper installation and operation of this control
could  result  in  damage  to  the equipment  and  possibly  even
personal injury. It is your responsibility to ensure that this con-
trol is  safely  installed  according  to  all  applicable  codes  and
standards. This electronic control is not intended for use as a
primary limit control. Other controls that are intended and cer-
tified as safety limits must be part of the control circuit. 