Specification
101-203
Effective: February 27, 2018
Supersedes: NEW
Submittal Data Information
Job: Engineer:
Contractor:
Rep:
ITEM NO. MODEL NO.
• M aximum Shut-off Head: 13 feet
• Maximum Flow: 11 gpm
•
M aximum Operating Pressure: 150 psi
(10 bar)
• M aximum Water Temp: 203°F (95°C)
• M inimum Water Temp: 36°F (2°C)
• E lectrical Specifications:
Voltage: 120V, 60 Hz
Single phase
Max. Operating Power: 44W
Max. AMP Rating: 0.54
• Equipped with a composite casing designed for
open loop potable water systems and closed
hydronic systems
• Not suitable for chilled water
• T aco circulator pumps are for indoor use only
• A cceptable for use with water or maximum
of 50% water/glycol solution in closed
hydronic systems
P
ump Dimensions & Weights
Electrical Data
Model Volts Hz Ph Max.Amps Watts RPM
All Models
120 60 1 .54 44 1440 - 3720
Motor
Type
ECM, Permanent Magnet, Thermally Protected
Casing: ............................................... Composite
Stator Housing: ............................... Composite
Cartridge: .......................................... Composite
Impeller: ............................................. Composite
Shaft: ...................................................... Ceramic
Bearings: ................................................ Carbon
Thrust Bearing: .................................. Ceramic
O-Ring & Gaskets: ................................EPDM
Model Number
(Part Number)
ABCDFGShip Wt.
in. mm in. mm in. mm in. mm in. mm in. mm lbs. Kg
006e3LC
VM1212-DY1-UP2A01
5
-1/2 140 4-7/8 124 2-5/8 67 3-1/4 82 5-1/8 130 5-1/8 130 3.5 1.6
Mounting Positions
D
C
B
F
G
A
ISO 228-G1
(DIN 259/BS 2779)
• Input: 120VAC, 50/60HZ, single phase, 6A
• Output: 120VAC, 50/60HZ, Single phase, 1/2 hp
(limited to 6 FLA, 36LRA)
• Sensor: NTC Thermistor, 10K ohm @ 77°F, B= 3392
• Fuse: 125V, 6A, Medium Acting 5x20 mm glass,
Littelfuse® p/n 0233006 mxp
• Ambient Operating Temp: 50-104°F, 10-40°C
0
06e3 Sp
e
cifications
006e3 Materials of Construction
SmartPlug Specifications
SmartPlug Components
FOR INDOOR USE ONLY
SmartPlug
Sensor
Sensor
Connector
Hot-Link Valve Materials of Construction
Body ...................................................................................Nylon
Thermal Disk Actuator .........................................Bi-Metal
O-Ring Seals ................................................................... EPDM
Integral Flow Check (IFC
®
):
Body, Plunger ............................................ Acetal
O-Rings ..........................................................EPDM
Screen ........................................................... 304 SS
Stem ................................................................Nylon
Actuator Cartridge ........................ Stainless Steel
Braided Flex Hoses ....................................... Stainless Steel
Connection
ABCDShip Wt.
in. mm in. mm in. mm in. mm Lbs. Kg
1/2” MNPT 4 102 4-7/16 87 1-3/4 41 2-1/2 64 0.37 0.17
Hot-Link® Valve Dimensions & Weights:
A
B
MINIMUM AREA
REQUIRED TO
MOVE STEM
D
Sensor
Strap
C
System Model Number