User's Guide

tLory User Guide
13
<Setting Sensing Cycle>
ORDER DESCRIPTION
1 Set Channel, Spreading Factor with Dip Switch
2 Turn on Switch 7 to activate tLory
3 Set LoRa of sLory or uLory in the same way of setting LoRa of tLory
4 - Enter an interval unit in the entry 48 and sensing cycle in the entry 49
(Refer to the General Manuals for table maps rather than the Quick Manuals)
* tLory is in the Sleep Mode except when it is sensing as it uses battery. It
collects data and goes back to Sleep Mode after the 3-second RX Mode.
Therefore, it is necessary to send LoRa packets to set the sensing cycle before
the device switches back to the Sleep Mode.
- Set the minimum time to 4 seconds or longer since the sensing cycle is 3-
second
The minimum of sensing cycle is 4 seconds. If it is set to be shorter than 4
seconds, the sensing cycle will be 4 seconds.
5 Enter the ID of the destination device in the entries 50 to 52
6 Enter the table number of the destination device in the entry 53
7 Enter the entry number of the destination table in the entry 54
<Remote Setting>
Users can change the setting remotely via LoryView when it is difficult to use switch for the
setup of LoRa while tLory is in use (when the installation location is not within easy reach).
The device will be activated and operated according to the value set in the table rather than
the value set via Dip Switch if the value of Switch Flag in the setting option is set to 1 with
reference to LoRa Port Process Table Map.
7. Table Maps
The port process of tLory supports the port process for temperature and humidity to
connect sensors with LoRa for data communication. The information in the table must be
read and written using LoryNet device ID, destination table number, and entry number in
order to activate each port or check the Generation Mode. A table map guides user device