GENIOX VOCLEAN IOM

43Components and Technical Specications
DuringthecourseofoperationofESP’s(electrostaticlters)residualgreaseanddustthathasnotowntothepanaccumulateson
collectorplates.ThisaccumulationcanreducetheefciencyoftheESPandcauseres.
Therefore, collectors may need to be removed and washed manually at frequent intervals (every 3 days).
Automatic washing system is offered as an option with the Geniox VOClean Ecology Unit in order to reduce the frequency of
manual washing.
“Figure40”showsthepanelandwashinggroupoftheAutowashSystem.
2 nozzles are used per washing group for each ESP collector.
A line from the boiler should be connected to the autowash system to deliver water at 60°C and at a minimum pressure of 2 bar.
This water is delivered to the nozzles after the addition of detergent at various intervals by means of the PLC inside the panel.
3-angle pans are used to drain the oil-water-detergent mixture that is formed during the washing process.
S.2 Autowash System
Table 3: ESP Technical Specications
Figure 39: ESP Panel
Technical specications of the ESP used in the Geniox VOClean Ecology Unit are shown in “Table 3” and the panel is shown in
“Figure 39”.
ESP 1500 Technical Specications
Power Consumption 20 Watts
Maximum Capacity 0,7m³/s
Power Supply 1” / 220-240V / 50 Hz
Filter Efciency %98
Operating Status
LED Indicator
Cam
Switch
Label
Panel
Door