GENIOX VOCLEAN IOM
38
Region Interval Instructions
Odor Neutralizing
Agent Level Indicator
2-4
Weeks
The odor neutralizing agent level varies according to the ow rate of exhausted air and the
amount of odor contained in the exhaust air.
On average use, 1 liter of odor neutralizing agent can last 3-4 weeks.
The quantity of odor neutralizing agent should be checked at specied intervals and topped
off as necessary.
This procedure can also be carried out on a daily basis without waiting for the odor
neutralizing agent to be depleted, and the agent can be topped of in the necessary quantity.
In order to add odor neutralizing agent, you can open the tank lid by turning in the
counter-clockwise direction. After the lling is completed, the lid can be screwed back on by
turning in the clockwise direction.
Excessively high odor neutralizing agent will cause overow and dirtiness inside the odor
neutralizing unit.
In such cases, the inside of the unit should be wiped with a moistened cloth.
R.6. Odor Neutralizing Unit
R.7. Heat Recovery Coil
WARNING
The power supply to the unit must be disconnected before performing tasks such as maintenance, cleaning, assembly.
People performing these tasks must wear protective equipment (safety goggles, gloves, etc.) and be qualied to perform
such tasks.
Contact with the odor neutralizing agent should be avoided.
WARNING
The odor neutralizing agent is not protected against explosions. It can cause sparks and can not be used in areas where
there is a risk of explosion.
The odor neutralizing unit must not be used without proper electrical grounding.
WARNING
The use of the odor neutralizing unit in conditions over 75% RH is not recommended.
The use of the odor neutralizing unit under 5°C or over 56°C temperature is not recommended.
Since air ducts downstream of the ecology unit will be under positive pressure, duct connections must be airtight to
prevent the odor neutralizing agent and odor particles from leaking out of these ducts into the atmosphere.
Region Interval Instructions
Fins That Increase the
Heat Transfer Area
1 Month
- 3
Months
Dust may gradually accumulate between the ns that are used for the purpose of increasing
the area of heat transfer in the heat recovery coil. This reduces the efciency of heat recovery.
For this reason, the spaces between the ns should be cleaned at regular intervals using
pressurized water or pressurized air. Brushes or similar tools can also be used for this purpose.
WARNING
The power supply to the unit must be disconnected before performing tasks such as maintenance, cleaning, assembly.
People performing these tasks must wear protective equipment (safety goggles, gloves, etc.) and be qualied to
perform such tasks.
Recommended Maintenance Interval