GENIOX VOCLEAN IOM
Contents
37
INFORMATION
Once you have completed the maintenance and cleaning procedures and started the ESP device, crackling or arcing
sounds can be heard initially as the system begins to load. This is completely normal.
WARNING
If the crackling and arcing sounds continue and if the green” in operation” lamp comes off, this means there is a problem
with the device. In this case cut the electrical supply to the unit and alert service teams.
The use of ESP’s under -10°C and over 60°C and 75% relative humidity is not recommended.
WARNING
Delaying maintenance can cause res.
Region Interval Instructions
UV-V Lamps,
Ballasts, and
Electrical Connections
1 Month
Visual checks should be performed on a regular basis to see whether the lamps are on or off.
There is a LED light installed on the ballasts outside the UV-V section to indicate whether the
lamp is on or not. The moment one of the UV-V lamps are off, this LED indicator light on the
lamp’s ballast will come on.
If UV-V lamps do not come on, electrical and socket connections should be checked. If there
are no
problems, the lamp must be replaced.
Dust can accumulate on the surfaces of lamps in time.
Before conducting a visual inspection to determine such accumulation, the power supply of
the ecology unit must be disconnected. After waiting 1 minute, the door of the UV-V section
should be opened. If there is dust, soot etc. on the surfaces of UV-V lamps, these surfaces
should be gently wiped with a moistened cloth.
The staff performing the cleaning should wear gloves. The lamps should be handled as gently
as possible during cleaning.
R.5. UV-V
INFORMATION
UV-V lamps should be replaced every 17,000 hours (approximately 1 year).
Different brands of UV-V lamps can have different strengths. Therefore they do not generate the same quantity of ozone.
Installing just any brand of UV-V lamp may lead to insufcient retention of grease and odor. For this reason, please
contact Systemair to install the right lamp. The use of UV-V lamps of different brands can nullify UL and CE certication.
The unit may be removed from warranty coverage.
WARNING
Incorrect installation, an incorrect setting, incorrect maintenance or improper use can lead to electric shocks, injury or
material damage.
Please contact a qualied installer, service agent or supplier for information and assistance.
WARNING
The main power supply switch of the unit must be turned off before installation, maintenance and cleaning operations.
Failure to do so can lead to injuries or death.
UV-V lamps are exceedingly high energy devices. Therefore, the rays generated by UV-V lamps should not come into
contact with eyes or skin. For this purpose, gloves, goggles and skin-covering equipment should be used.
UV-V lamps contain small quantities of mercury. In case the lamps break, the areas containing the broken parts and the
areas
contaminated with mercury should be cleaned with a moist cloth and by wearing gloves.
Since UV-V lamps are exceedingly high energy devices they cause ozone gas to be formed. Above a certain ppm value
ozone gas has a harmful effect on organisms or can cause the organism to die. You should not stand at the discharge
section of the ecology unit while the unit is in operation, and you should not breathe the air that comes out.
Since air ducts downstream of the ecology unit will be pressurized and since ozone gas will pass through these ducts, air
leaks from these ducts should be prevented. Otherwise, any living creates that are in the environment where ducts are
located can be harmed.
Recommended Maintenance Interval