GENIOX VOCLEAN IOM

33Recommended Maintenance Interval
O Instructions for machinery where these are regularly to be transported
P The operating method to be followed in the even t of breakdown. Safe restart.
Q Adjustment and maintenance operations
R Recommended maintenance intervals
R.1 Casing
Pay attention to several sharp edges during dismantling and disposal of the unit. To avoid injury, CE-marked cut-resist¬ant gloves
as well as helmet must be used. The measures are described further in the Maintenance, Dismantling and Disposal Manual.
The subject in the Machinery Directive about machinery that are regularly to be transported does not exist for the Geniox VOClean
ecology units, because those units are specially made for one intended application.
Use the below mentioned procedure in the event of breakdown or blockage:
Switch off the power and lock the automati c cir cuit breaker by padlocks in the off position.
Remove the reason for breakdown or blockage.
Follow the start-up procedure described in chapter K.
Must be performed by skilled technicians.
In connection with demands for compensation, Systemair must have full and unhindered access to all relevant reporting on service,
repair,modicationandusesincetheunitwastransferredfromSystemairtoatransportcompanyattheSystemairfactory.Itisa
condition for compensation that maintenance outlined on the following pages has as a minimum been performed.
By performing the simple cleaning and maintenance procedures described below, following the relevant warnings and taking the
necessary measures, most problems will be spotted and a full downtime for the system will be avoided.
Themaintenanceintervalsspeciedmayvarydependingonspecicoperatingandenvironmentalconditions.Thereforeanannual
detailedexaminationisneededinadditiontotheperiodicmaintenancetasksspecied.
N.2 General disassembly - sharp edges
WARNING
The specied maintenance and cleaning intervals are recommended values. It would be the more correct approach for
you to determine your own periods according to your degree of use and your cuisine.
Region Interval Instructions
Internal Unit Surfaces
3
Months
Grease and dirt can accumulate on internal surfaces (particularly on the edges of bypass
plates) since greasy, smoky, and dusty air will pass through the unit.
These residues may cause bad odors, sticky areas, and corrosive effects within the air
handling unit.
Wipe internal surfaces, especially the edges with a clean and moistened cloth at
recommended intervals.
External Unit Surfaces
6
months
Dust will accumulate on the unit, depending on the environment in which the unit is located.
This may lead to bad odors and corrosion on the unit.
Wipe external surfaces of the unit with a clean and moistened cloth at recommended
intervals.