GENIOX VOCLEAN IOM

29
Figure 33: Position of the odor neutralizing units
pipe inside the ecology unit
K.3.10 Odor Neutralizing Unit
During initial installation of the odor neutralizing unit, care should be taken to ensure that the angular section of pipe which
extends into the ecology. If the angular section of the pipe is facing another direction, the pipe should be rotated so it faces the
right one. Otherwise the air inside the air handling unit will enter the pipe and hinder the function of the odor neutralizing unit.
Sincethepipesoftheodorneutralizingunitttogethertightly,careshouldbetakentoensurethattheyarenotdislodged.
If the electrical connection of the odor neutralizing unit is to be performed on site, the connection should be made according to
220-240V/1 Phase/50 Hz.
Air Flow The Line Marking the Center
of the Unit in the Direction
of Air Flow
INFORMATION
Due to the working principle of the odor neutralizing unit, the ecology unit on which the device is installed and the ducts
downstream of the ecology unit must all be grounded. Otherwise the ionized odor neutralizing agent in vapor form will
not electrically adhere to all odor particles.
Before operating the ecology unit, the odor neutralizing agent must be lled in the ll tank opening shown in “Figure 44” and the
level of the ll should be observed from the level indicator window seen at the bottom right of the photo.
INFORMATION
During the lling of the odor neutralizing agent, the fan speed setting in the odor neutralizing unit should be switched to
the off position.
As the ecology unit is brought online, the “Power button seen in “Figure 44” must also be pressed.
When the system begins operation, the amount of odor neutralizing agent vapor can be adjusted by using the fan speed setting
seen on the top left of “Figure 44”. When this setting is adjusted to the highest value, 90% of the odor can be eliminated from air
that passes through at a ow rate of 15,000m³/h.
The proportion of odor elimination based on the ow rate of exhaust air can be calculated based on this percentage.
Figure 34: Internal view of the odor neutralizing unit panel
Start-Up