GENIOX VOCLEAN IOM
27
Then,theblue“AlarmReset”buttonseenon“Figure29”shouldbepressed.Anytimethisbuttonispressed,thered“Stop/Reset”
buttonseenin“Figure40”shouldbepressedsubsequently.
The“Start”buttonlocatedtotheleftofPLCasseenin“Figure31”shouldbepressedtostartthewashcycle.Oncethisisdone,the
green light will come off and the orange light will come on.
The PLC screen displays the current stage of the wash cycle.
NOTE: If you want to urgently stop the washing process, you need to press the “Stop/Reset” button seen on “Figure 30”.
The washing procedure involves various steps. These are:
• Stopping the operation of the ecology unit
• Waiting for the ESP to discharge and for the fan to stop
• Pre-wash
• Waiting for the water to stop dripping
• Detergent spray
• The reaction between the detergent and grease
• Rinse
These steps are repeated several times which concludes the washing procedure.
The fan is operated for a certain amount of time to dry the wet ESP collectors, then the system is placed on full standby for a period
of time.
Figure 29: The alarm reset procedure and the text
displayed on the PLC screen
Figure 30: The Stop/Reset Button
Figure 31: The Start Button
When the alarm reset button
is pressed
Start-Up