K.3.8 Autowash System
230V, 50Hz electrical supply should be connected to the unit for the Autowash system to operate.
Once the water pipes have been installed as instructed in the assembly section, the valve for the water that will be supplied to the
Autowash system should be opened.
Thewaterpressureshouldbereadfromthemanometershownin“Figure24”andthereadpressurevalueshouldbearound2bar.
Note: Maximum permissible pressure is 7 bar.
Thedetergenttankseenin“Figure24”shouldbelledwithdegreasingdetergenttocleanthegreasefromelectrostaticlters.
Then the power supply to the Autowash system panel should be turned on. At this stage, the orange lamp on the panel seen in
“Figure25”whichindicatesthatthesystemisinoperationwilllightup.
Transformer
Manometer Pressure
Switch
Dosage
Pump
Detergent
Tank
The PLC
Display
PLC
Start
Figure 24: Internal setup of the Autowash system
Figure 25: Indicator lights and buttons on the
panel
Start-Up