GENIOX VOCLEAN IOM

24 Start-Up
K.3.4 Damper motors
K.3.5 Filters
K.3.6 Fan and Fan Motor
K.3.7 ESP
On/off damper motor, without spring return function. Torque is 5-20 Nm and run time is 150 seconds.
For units not equipped with damper motors, damper blades should be opened with the help of the damper shaft rotating lever
before starting the unit. In automated models, no manual intervention should be made on the damper.
Although the electrical cables leading to the damper motor are wired to the unit panel prior to shipping the unit, the cables may
have been dislodged during shipping. For this reason, electrical connections should be checked.
Metallicltersarepre-installedattheSystemairfactorytopreventdamagetoionizersfoundonESPcollectorsandtopreventsolid
particles from entering collector plates.
Baglters,EPA/HEPAlters,andactivatedcarbonltercartridgesaresentinsideaboxtopreventthemfrombecomingdirtyand
causinglossofefciency.
Careshouldbetakentoensurethatltersareinstalledasexplainedintheinstallationsection,andthattherearenomissinglters.
Careshouldbetakentoensurethatbagltersareinstalledvertically.Otherwisethepocketswilloverlap,whichwillleadtopres-
sure loss.
Careshouldbetakentoensurethatactivatedcarboncartridgesaretightlyttedontheslotsoftheplate,andthattheywillnot
move out of position. Otherwise air will leak from gaps in the cartridge slots and odor elimination will not be effective.
Although the electrical cables leading to the fan motor are wired prior to shipping the unit, the cables may have been dislodged
during shipping. For this reason, electrical connections should be checked.
Since a door switch is installed on the door of the section housing the fan and fan motor, the fan will not operate when the door of
this section is open. Care should be taken to ensure that this door is closed.
Checkwhetherthefanmovesfreelywithoutbeinghinderedbythebody,exibleconnectionsorcables.
Rotate the fans manually to check whether they turn easily. Make sure there are no foreign substances in the fan section.
Although no additional wiring is needed since the unit will be supplied with all electrical cabling already installed, cables should be
checked lest they have been dislodged during shipping.
Care should be taken to ensure that the open/shut button or cam switch that can be located on the ESP door on the ecology unit is
in the open position.
If any component section has a door switch and if the door to the section is open the ESP will not operate. Therefore care should
be taken to ensure that doors are closed.
WARNING
Bag, EPA, HEPA and Active Carbon lters can not be washed or cleaned.
These lters should be replaced when their useful life has ended.