Check before commissioning
Thetightnessofthethreadedjoints;tightenthemifrequired,
theproperfunctioningoftheheatingcoilautomaticanti-frostprotection,beforetheheatingcoilislledwiththe
heat transfer medium,
the tightness of the piping joints,
the proper functioning of the automatic shut-off of the supply of heating medium into the heating coil at a heating
medium temperature above 70 °C, to protect the electric motor against overheating,
the proper functioning of the automatic condensate discharge pot.
Medium lling
Partially open the steam valve and wait until steam begins to emerge from the draining and venting valve.
Close the draining and venting valve and fully open the steam valve.
Caution
Takecareofpossibleveryhighmediumtemperaturewhendraining.
Medium draining
Close the steam supply valve and open the draining valve.
Oncedrainingisnished,openthesteamvalveonceagaintoletallthecondensatedrainfromthesection–until
steam emerges.
Close the steam valve.
Let the draining valve open until the next restart.
Upondrainingtheheatexchanger,drythetubebankbyblowingitwithcompressedairtoabsolutelypreventthe
riskoffreezingofanyresidueofheatingmediumorcondensate.
Protection against the fan motor overheating
In the event of high steam temperatures, arrangements must be provided to protect the fan electric motor from
overheatingduringunitidling;thisisachievedbyautomaticallyshuttingoffthesupplyoftheheatingmediumintothe
heating coil and continued operation of the fan for a certain period of time (3 to 5 min) after the unit operation has