KA IMO 2021 6 V2.1

systemair 39
3.4.3 Metal lter
Caution
See also section 3.1 General instructions and 3.4 Filter.
See the values in the selection program data and on the nameplate.
Commissioning
Ifnotalreadyinstalled,inserttheltercassettesintotheframe:
insertthecassettesonenexttoanother,untiltheentirecrosssectionofthesectionislled,
checkthatsealingtapeisappliedonthesectionservicedoor,
checktheinstallationofthepanunderthemetallter,
checktheconnectionofthepressuremeasuringhosestothepressuremeasurementportsandconnectthehosesif
necessary.
Maintenance
Replacetheltercassettes:
slideouttheltercassettes,
drain/cleanthepanbelowthelter,
clean the section casing if necessary,
insertcleanltercassettes,
checktheconnectionofthepressuremeasuringhosestothepressuremeasurementportsandconnectthehosesif
necessary.
A soiled metal frame may be washed in hot water with cleaning agent added, observing the cleaning agent
manufacturers instructions and ensuring the proper water temperature.
CleanedcellsmaybeimpregnatedwithBAorMAviscose,bymeansofsoakingorspraying.