KA IMO 2021 6 V2.1

38 systemair
Replace the lters:
Loosentheclosingproles,
slideoutthecontaminatedltercassettes,
clean the section casing if necessary,
inspect the condition of the sealing tape on the sealing contact surface and repair or replace the tape if necessary,
insertcleanandundamagedlters.
Caution
Forltersectionshigherthan1900mm,thedoorisdividedbyheight.Toreplacetheltersattheplace
ofthepartitionprole,itisnecessarytounscrewitandscrewitbackafterreplacement.
3.4.2 Dirty side removable cassette lter
Caution
See also section 3.1 General instructions and 3.4 Filter.
See the values in the selection program data and on the nameplate.
Commissioning
Ifnotalreadyinstalled,insertthebagltersintothesupportframe:
checkthatthesealingtapeisappliedonthebaglterframe,
insertthebaglterinsuchawaythatthebagshangfreelythroughtheframeopeningandarenotcompressed,
pinched or damaged,
ineachframecorner,insertawirespringtopressthelterbagagainstthesealingtapeontheframe,
wheninstallingandjoiningshipmentunits,observetheruleofinsertingtheltersintotheframesoastoensure
thattheairowpressesthemagainstthesealingtapeontheframe.Anyairowactinginthedirectionoppositeto
the direction of the acting wire springs is not allowable,
checktheconnectionofthepressuremeasuringhosestothepressuremeasurementportsandconnectthehosesif
necessary.
Maintenance
Replacethelters:
ltersmayonlybereplacedfromthenon-lteredairside,
removethewiresprings/loosentheblockproles,
slideoutthebaglters,
clean the section casing if necessary,
inspect the condition of the sealing tape on the sealing contact surface and repair or replace the tape if necessary,
insertcleanandundamagedlters.