KA IMO 2021 6 V2.1

34 systemair
Wiring diagram
1,2 PE green/yellow Protective earth
3 L1 Black Power supply
4 L2 Black Power supply
5 L3 Black Power supply
6 NC White 1
Statusrelay,oatingstatuscontact,breakforfailure,contactrating250VAC/2A(AC1)/min.10mA;reinforced
insulation on supply side and basic insulation on control interface side
7 COM White 2
Statusrelay,oatingstatuscontact,breakforfailure,contactrating250VAC/2A(AC1)/min.10mA;reinforced
insulation on supply side and basic insulation on control interface side
8 0-10V Yellow Analoginput(setvalue),0-10V,Ri=100kΩ,adjustablecurve,SELV
10 RSB Brown RS485interfaceforMODBUS,RSB;SELV
11 RSA White RS485interfaceforMODBUS,RSA;SELV
12 GND Blue Reference ground for control interface, SELV
13 +10 Red
Fixedvoltageoutput10VDC,+10V±3%,max.10mA,short-circuit-proofpowersupplyforexternaldevices(e.g.pot),
SELV
Check before commissioning
Themountingofthefanontheframeandthemountingoftheelectricmotoronthetensioningbracket,
theparallelismofthemotordriveshaftandofthefanshaft;inthecaseofdeviation,adjusttheelectricmotorby
meansofthetensioningbracket,andoncetheadjustmenthasbeencompleted,rmlytightenallthescrews,
the mounting of the rotor on the shaft and its free rotation in the casing,
the mounting of the vibration isolators,
the correct installation of the grounding,
the correct installation of the electrical connections and their operation (fuse sizes, contactors, thermal protection),
for the presence of any tools or other foreign materials in the section,
the mounting of all the covers and doors.
Thermalprotectionisessentialforthesafetyoftheelectricmotor,therefore,beforestartingthemotor,checkif
ithasthecorrectsettingsforthenominalcurrentofthemotor,andcheckitsoperation.Oncethistesthasbeen
successfully completed, seal the thermal protection device.