KA IMO 2021 6 V2.1

systemair 29
3. COMMISSIONING AND MAINTENANCE
Caution
Theunitcommissioningmayonlybecarriedoutbyaqualiedprofessional.Beforestartinguptheair
handlingunit,checkalltheelectricalconnectionsandunitcontrolsettings.
3.1 General instructions
Before maintenance
Thepowersupplymustbeswitchedoffcompletelyandtheserviceswitchmustbeswitchedoffandlocked.
Due to the frequency converter, it is necessary to wait at least 15 minutes.
Itisnecessarytocheckwhetherallrotatingpartsarestationary(fan,belts,rotaryheatexchanger,blinds).
Itisnecessarytocheckwhetherthetemperatureintheheatexchangersandhydraulicsystemshasadaptedtothe
ambient temperature.
ThePMmotorshaftmustbeblocked.Externalinuencesonmotorrotationgenerateelectriccurrent.
The unit must not be in an explosive atmosphere during service.
Protectiveclothingandfootweararerequired(helmet,maskforchanginglters,glovesandshoes…).
Allserviceaccessoriesisrequired:tools,serviceswitchlockkey
As the entire electrical installation is switched off during servicing, external, separate lighting is required.
Aspecialkeyisrequiredtoopenandclosetheservicedoor.
After maintenance
Clean any dirt from maintenance.
Checkthatallmechanicalandelectricalcomponentsareinplaceandsecurelyfastened.
Makesurethatnooneisinthedangerareaofthedeviceoritssurroundings.
Makesureyouhaveremovedalltoolsorotherobjectsfromthedevice.
Closetheservicedoorandlockthehandlelocks.
During maintenance
Checktheconditionofthesection.Incaseofdirtorcorrosion,immediate
cleaning is required.
Checkthegasketatthecontactofthepanelordoorandcasing.Ifthegasketis
damaged or detached, it must be completely removed, the surface cleaned and
gasketreplaced.