Geniox NA Product Guide Specification
Systemair
Geniox
Series
Semi Custom AHU 
Item#  
23
72
13
-
11
by making available at the unit manufacturer’s plant a repaired or replacement part. 
B. 
VRF Module (If Applicable) The supplier of the VRF components installed at the factory shall 
be responsible for the service and warranty of the (LG/Daikin/Mitsubishi/ Samsung) 3rd party 
VRF kits, (coil(s)) and any applicable components. 
PART 2  PRODUCTS 
2.1 
MANUFACTURER 
A. 
Systemair Inc., 8 Rouse Street, Tillsonburg, Ontario N4G 5W8, Canada.  Toll Free
877-797-
2471.  Phone 519-688-6363.  Website www.systemair.net.  E-mail
sales@systemair.net. 
2.2 
AIR HANDLING UNITS 
A. 
Air Handling Units:  “Geniox Series”. 
Specifier Notes:  Specify required model.  Consult Systemair Inc. for assistance in determining air 
handling unit model for the specific application. 
[Select one model only] 
1.  Model:  Geniox 10, 12, 15, 20, 25, 30, 35, 40 
2.  Indoor, outdoor, air handling unit(s). 
3.  Airflow Control: [Variable air volume, Constant air volume]. 
B. 
General 
1. 
Each Unit or Group of Units:  Capable of operating in any mode independently 
or
dependently of other systems. 
2. 
Capable of changing modes with no interruption to system operation. 
3. 
Listed under CSA C22.2, No. 236/UL 1195. 
4. 
Wiring:  NFPA 70. 
5. 
Performance:  As scheduled on the Drawings. 
6. 
Equip with control systems from the manufacturer or third party, see controls. 
7. 
Perform all functions necessary for operation. 
8. 
Ventilation to Building:  Not to cease in any mode based solely on operational 
temperature
of -30 to 104 degrees F (-34 to 40 degrees C). 
9. 
Capable of operating in winter and summer conditions without imbalance or loss 
of
ventilation capacity greater than specified in design. 
C. 
Unit Cabinet 
1. 
Panels and access doors shall be constructed as minimum 2.4-inch (60-mm) nominal 
thickness with Polyurethane injected foam insulation with an R-value of no less than 
R-14. The outer panels shall be constructed of G90 Galvanized 22-gauge steel. The 
inner liner shall be constructed of G90 galvanized 22-gauge steel 
2. 
The casing and frame design shall be thermally broken so as to negate thermal bridging 
between the interior and exterior of the unit. 










