Geniox NA Product Guide Specification
Systemair
Geniox
Series
Semi Custom AHU 
Item#  
23
72
13
-
17
C22.2 No236. 
2. 
Electrical Power:  208V/3Ph/60Hz, 460V/3Ph/60Hz or 575V/3Ph/60Hz. 
3. 
Internal Electrical Components:  Factory wired for single-point power connection. 
4. 
Standard Main Non-Fused Disconnect 
5. 
Standard Short Circuit Rating = 5kA 
6. 
Electrical Box Components:  Accessible without stopping unit or opening unit doors. 
7. 
Electrical Box: 
a. 
Isolated from airflow paths. 
b. 
Protect integral wires and connections. 
8. 
Controlled by integral microprocessor controller. 
2.3  AIR HANDLING UNITS CONTROLS 
A.  General 
1.  All air handling units will be equipped with a factory installed and configured DDC 
controller. 
a. 
The controller shall be pre-programmed for ventilation heating cooling 
applications; no further programming will be required. 
b. 
All controller settings, I/O points, configurations, functions, set-points, time 
schedules, and control modes shall be modifiable via PC software or network. 
c. 
Access rights: there shall be three different program access levels: Admin, 
Service, Operator and Normal. Each level with have a password and grant the 
following level of access: 
d. 
Network level(BAS System): full read/write access to all settings and parameters 
in all menus. 
e. 
Service level: access to all menus except the submenus under Configuration: In- 
and Outputs & System. 
f. 
Normal level: only permits changes in "Running mode" and read-only access to a 
limited number of menus. 
g. 
The controller must be capable of supporting schedule timers and system 
integration to Building Management Systems via BACnet MS/TP 
h. 
Controller Communications: Via BACnet MS/TP communications bus. 
i. 
Control Wiring: Installed in system daisy-chain configuration from unit to BAS 
controller and to other units, if applicable. 
j. 
Network Wiring: Two wire RS-485. 
k. 
VRF Module if Applicable: 
•  The manufacturer shall provide an air handling unit with 
integral factory-supplied and installed controls specifically designed and 
programmed to integrate with the (LG/Daikin/Mitsubishi/ Samsung) 3rd 
party VRF kits. 
•  (Daikin only) The manufacturer shall provide a controller 
compatible with the Daikin 'W' type controls. 
•  Customer provided VRF sensor (if applicable) shall have 
a wire length of at least 14 ft. 
2.  Controls by others installed at AHU Manufacturer in AHU Manufacturer supplied standard 
Electrical Panel 
a. 
Controller must fit the space/volume specified. Dimensions must be approved by 