| Instructions for unloading on the site as well as installation and connection
I.3 Installation - electrical
I.3.1 Video instruction and overview
Note:
Instructions about easy, quick and safe installation of sensors and cables in a 3–minutes video. The video is
available on YouTube.
https://youtu.be/y3oB9z44MCk
The cabinet is always placed in the section with the sup-
ply air fan. Hereby the air flow around the cabinet is al-
ways preheated or during hot summers eventually
precooled by the heat exchanger.
Cable entry is always in the bottom of the air handling
unit
The position of components is shown and described in Annex 2.
Connections to terminals are shown in the wiring diagram.
When control of constant pressure in the ducts (also called demand controlled capacity) is required, the pressure trans-
mitters must measure in the duct system at places where all pressure changes can be registered accurately for reliable
pressure control. This placement is left to the customer’s free choice.
It is important to achieve a constant pressure also for the most faraway diffusers.
I.3.2 Wiring diagrams
The wiring diagrams are printed in separate manuals delivered with the units.