Rigid duct connection at the Geniox Core unit is available with 20 mm or 30 mm flange for LS profile and screw clamps.
Please check the order confirmation or the data in the annex 2 concerning the size of the flange 20 mm or 30 mm.
Furthermore the rigid duct connection is always with a
8,5 mm hole in each corner of the flange.
Use 8 mm bolt with nut in each corner and a sufficient
number of screw clamps with a distance between screw
clamps that not exceeds 300 mm to hold the duct,
damper, coil or attenuator tight together
Size of duct connections at the 7 sizes of Geniox Core units
Size of unit Width in mm Height in mm
10 1000 400
11 1100 450
12 1200 500
14 1400 600
16 1600 700
18 1800 800
20 2000 900
I.2.10.1 Dampers for installation in ducts
If the damper is mounted on the rigid duct connection of the air handling unit, the installer must support the damper
further by brackets or suspension prior to mounting of ducts. Ducts as well as dampers must be insulated according to
local guidelines
I.2.10.2 Coils for installation in ducts
The duct connection is available with 20 mm or 30 mm flange for LS profile and screw clamps. Furthermore always a
8,5 mm hole in each corner of the flange.