Geniox Core Knock Down Ready

Additional sections (only for sizes 16, 18 and 20)
|
35
E.3 Reassembling the section
Reassemble the parts of the casing and reinstall the components in the opposite sequence of separation described
above.
Note:
Application of the delivered mastic and placing of 3 different types of self-adhesive flexible sealing lists are
important in order to achieve the air-tightness that corresponds to Eurovent certified values for this air
handling unit.
This mastic must be applied to all connections between
vertical profiles and plastic corners and between the walls
with filters and the casing, between the walls with fans
and the casing, and around dampers. All places are
marked with blue colour on the unit. The number of
metres that must be applied appears from the table
below.
This is to some extent illustrated with blue colour in the
drawing below.
Place this self-adhesive sealing list on vertical edges that
are marked with green colour on the unit. This is illus-
trated with green colour in the drawing below.
Place this self-adhesive sealing list on horizontal edges
that are marked with black colour on the unit. This is illus-
trated with black colour in the drawing below.
Place this self-adhesive sealing list on the profiles of one
of the sections to achieve fully air-tight connection be-
tween two sections. The profiles of the section are
marked with red colour. This is illustrated with red colour
in the drawing below.
The number of metres to which mastic must be applied.
Size of unit Unit with rotary heat exchanger
16 18 m
18 20 m
20 22 m
output |