Geniox Core Knock Down Ready
Table Of Contents
Section with counterflow heat exchanger |
25
D.4 Reassembling the section with counterflow heat exchanger
Reassemble the parts of the casing and reinstall the components in the opposite sequence of separation described
above.
Note:
Application of the delivered mastic and placing of the self-adhesive flexible sealing list is important in order
to achieve the air-tightness that corresponds to Eurovent certified values for this air handling unit.
This mastic must be applied to all connections between
vertical profiles and plastic corners and where parts of
the counter flow heat exchanger are assempled. All pla-
ces are marked with blue colour on the unit. The number
of metres that must be applied appears from the table
below.
This is to some extent illustrated with blue colour in the
drawing below.
With green colour on the unit is illustrated where this
self-adhesive sealing list must be placed. This is to some
extent illustrated with green colour in the drawing below.
The number of metres to which mastic must be applied.
Size of unit Unit with counter flow heat exchanger.
10 14,3 m
11 15,7 m
12 16,3 m
14 18,3 m
16 21,1 m
18 22,3 m
20 25,1 m
output |