Communication Manual
Table Of Contents
  Chapter 1 │About this document  4 
Chapter 1 About this document 
Introduction   
This  document  describes  Access  controller  application  communication  possibilites  in  terms  of 
integration as communication slave via EXOline, Modbus and BACnet. 
Software version 
Access version 
Available 
V4.0-1-04 
Modbus are available 
V4.0-1-05 
later 
EXOline, BACnet and Modbus are available 
NaviPad 1.1.0.184  
later 
With Ethernet menu, static IP setting 
Release column in register tables further down in this document tells from which software release 
variables was introduced or changed. 
Signal types 
All signals accessible from a SCADA system are declared in a spreadsheet referenced in Tables of 
variables with register addresses.  
EXOL type 
The EXOL type of the signals: 
R = Real (-3.3E38 - 3.3E38) 
I = Integer (-32768 - 32767) 
X = Index (0 - 255) 
L = Logic (0/1) 
Modbus type   
The Modbus type of the signals: 
0x = Coil Status Register (1bit)  
1x = Input Status Register (1bit)  
4x = Holding Register (signed, 16bit or 32bit word) 
3x = Input Register (signed, 16bit word or 32bit float) 










