  Chapter 2 │System integration  10 
Watchdog 
Access from software version 4.1-1-00 is capable of supervising communication recieved from a 
BMS  master.  One  slave  communication  protocol  can  be  monitored  at  a  time.  If  no  active 
communication from the BMS master is detected before the watchdog timeout elapses, an alarm 
message is generated. 
BMS watchdog (Activation of protocol) 
Upon  delivery, the  BMS  watchdog  is  disabled  as  default.  Activation  and  configuration  of  BMS 
watchdog is done via controller web menu Configuration / System settings / Communication / BMS 
watchdog 
BMS protocol 
To enable BMS watchdog, change the setting “None” to the protocol used for BMS communication. 
Supported BMS slave protocols are EXOline, Modbus and BACnet. 
Watchdog timeout 
Configure the watchdog timeout setting between 10 to 3600 seconds (1 hour), default 60 seconds. A 
byte counter of received bytes is supposed to change since the last cycle. If counter has not been 
changed during the watchdog timeout setting the communication is considered faulty and an alarm 
message is generated. 
Communication fault BMS master 
When a communication fault with BMS is detected, values from BMS should be considered invalid. 
The alarm is configured default as Class C with no action. 
Sensor value via BMS 