3060386 Geniox OIPM

Geniox Air Handling Unit - User Manual | 3060386
Following months
Service Start-up 1 2 3 4 5 6 7 8 9 10 11 12
Wheel bearing lubrication
Bearing bolt tightness
Driving belt tension and wear*
AirLoop seals adjustment
4.6 Recommended Maintenance Schedule
*Followinganydrivingbeltadjustments,thebeltshouldbeveriedagainafteramonthandeveryyearthereafter.
Following the service schedule above and keeping close records on your energy recovery wheel will insure trouble-free operation for
years to come. To keep your warranty in effect these services are required. This should be kept up-to-date during the warranty period.
LOW FRICTION SIDE & CENTER
Thelowfrictionsideandcentersealarecontactsealsxedtothewheelframe.Themiddlesealsarelocatedbehindthepillowblock
bearings. The side seals are installed on the side of the rotor, along the depth dimension. They are factory installed and adjusted. No seal
adjustmentisrequiredintheeld.
Media Cleaning
Duetotheirinnerlaminarowandself-cleaningfeature,theI4wheelsareresistanttodustbuild-ups.Asnoparticlewillaccumulate
inside the media, only the edges need to be cleaned.
Ifthewheelapplicationissuchthatcleaningisneeded,avacuumcleanerwithsoftbrushtipandcompressedairwithaatnozzle
blowgun (70 psi) is recommended to clean both sides of the media.
Asalaststep,amicroberhumidclothcanbeusedtowipethesurfaceofthewheel.
It is not recommended to use any type of solvent or detergent on the energy recovery wheel.
Caution
While cleaning the wheel media, take care not to apply too much pressure to avoid damaging the wheel surface. It is not
recommended to use any type of solvent or detergent on the energy recovery wheel.
4-11 | ERW maintenance