3060386 Geniox OIPM

Geniox Air Handling Unit - User Manual | 3060386
Note:
Make sure the contact wheel rests entirely on the rotor perimeter.
Figure: Incorrect Contact Wheel Alignment
3. Once correctly positioned, fully install the 2 top self drilling screws on both inner sides of the I4 vertical tubing.
4. Using 2 self drilling screws, fully install the bracket of the EDD assembly through 1 bottom hole mark (1) on both inner sides of the I4
vertical tubing.
Caution
Do not allow a visible space between the contact wheel and the I4 wheel. While the wheels rotate, a maximum of 1/32”
of space is allowed.
2. Using clamping tools, adjust the EDD assembly into the correct position on the I4 corner tubing.
1
Figure: Bottom Screw Placement
4-7 | ERW maintenance