Geniox NA Product Guide Specification

Systemair
Geniox
Series
Semi Custom AHU
Item#
23
72
13
15
9.
Drain pan shall allow visual inspection and physical cleaning to entire surface of the
pan without removal of the coil.
10.
Bypass Module for Hydronic Coils (If applicable): The manually adjusted bypass coil
profile plates shall be constructed with 18 gauge galvanized steel. The profile plate
openings shall be sized to ensure a balanced air pressure drop across the coil and
profile plate. This enables proper mixing downstream of the coil and the bypass
module.
11.
Hydronic Coil Control Valves
a.
Shall be provided by the [AHU manufacturer, Field installed by the Contractor]
b.
Wiring shall be installed by [the AHU manufacture to the control panel by AHU
manufacturer, by the Contractor]
H.
VRF Module
1.
The manufacturer shall provide an air handling unit with factory installed
(LG/Daikin/Mitsubishi/ Samsung) VRF 3rd party VRF package integral to the unit and
fully assembled, including the customer selected and required EEVs and
communication boxes. All VRF components shall be mounted internal to the unit with
adequate service access and clearances, externally mounted installations on the front
or back panel will not be accepted. Separate power feed to VRF components to be
provided on-site by client.
2.
a.
The unit shall be provided with a customer selected and supplied, Systemair approved
primary VRF coil (and Hot Gas reheat coil - if applicable only with LG/Samsung). The
DX coil(s) shall be integral to the air handling unit and factory-installed in the coil
section with a stainless steel double sloped drain pan. The coil(s) shall be factory piped
to the customer supplied EEVs and wired with communication boxes as required for
full integral connection and integration of the VRF system. The refrigeration system
shall include a factory pressure test and will be stubbed out to a common connection
point for field connection. Systemair shall be provided with the refrigerant network
diagram indicating specific refrigerant pipe sizes. The customer shall accurately size
coils and EEVs compatible with the remote VRF condensing unit(s) to ensure the
performance of the VRF system.
b.
OR The unit shall be provided with an empty section for the customer field supplied
and Systemair approved primary coil (and Hot Gas Reheat coil - if applicable only with
LG/Samsung) with a stainless steel double sloped drain pan for the field installation of
the coils. The customer shall provide and pipe the primary VRF coil (and Hot Gas
Reheat coil - if applicable only with LG/Samsung) to the EEVs and wire with
communication boxes as required. The customer shall accurately size coils and EEVs
compatible with the remote VRF condensing unit(s) to ensure the performance of the
VRF system.
I.
Electric Heater
1.
Electric heater shall be factory installed ETL listed open wire resistance heater with a
single point power connection for the unit and heater.
2.
Enables unit to perform in extremely cold climates to preserve performance and ensure
continuous supply of air or provides temperature control of supply air.
3.
Electric heater shall be constructed of high nickel-chromium alloy resistance wire (80%
Ni/20%Cr)