3060386 Geniox OIPM
3060386 | Geniox Air Handling Unit - User Manual
EDD Contact Wheel Adjustment
1. Using 2 self drilling screws, install the bracket of the EDD assembly through 1 top hole mark on both inner sides of the I4 vertical
tubing.
Caution
At this stage, do not install screws fully to allow for further adjustments.
2. Refer to the “A” dimension (1) in the drawing below, identify and place marks (2) where the top 2 holes of the motor holder bracket
and section base frame meet.
3. Place marks 5/8” (3) from the inside of the I4 corner tubing on both sides.
A
5/8
2
1
3
(A) DIMENSION TABLE
Wheel Ø A DIMENSION (in) + 1/4
48 7-
5
/
8
*
54 8-
1
/
4
62 10
70 11-
3
/
4
78 13-
1
/
4
84 14-
3
/
4
88 15-
3
/
4
96 17-
3
/
8
108 20-
3
/
4
120 23-
3
/
4
132 25-
3
/
4
*MIN FOR Ø48 I4 MODEL
(-0” +
1
/
4
”)
ERW maintenance | 4-6