| Connection of EC fan motor, diagnostics/faults and configuration of speed control
LED Code Relays
K1*
Cause
Explanation
Reaction of Controller
Adjustment
9 x 1
Cooling down period power module
Cooling down period power module for approx.
60 sec.
Final shutoff after 2 cooling-off intervals see code
6
Power module cooling down period for approx.
60 sec.
Final shutoff after 2 cooling-off intervals see code
6.
11 x 0
Error motor start
If a starting command is given (enable available
and Setpoint > 0) and the motor does not start to
turn in the correct direction within 5 minutes, then
an error message will appear.
If it is possible to start the motor in the target
direction of rotation after the error message, the
error message will disappear
Should a voltage interruption occur in the mean-
time, the time taken up to the switch off will begin
again.
Check if motor is freely rotatable.
Check if the fan is driven in reverse direction by
an air stream (see Behaviour in rotation by air
current in reverse direction).
12 x 0
Line voltage too low
If the DC-link voltage drops below a specied limit
the device will switch off.
If the line voltage rises above a specied limit
within 75 seconds, then the controller will attempt
to start.
Should the line voltage stay below the specied
limit for more than 75 seconds, the device will
switch off with an error message
13 x 0
Line voltage too high
Cause to high input voltage
If the line voltage increases above a specied
limit, the motor will switch off.
If the line voltage drops below the specied limit
within 75 seconds, then the controller will attempt
to start.
Should the line voltage stay above the specied
limit for more than 75 seconds, the device will
switch off with an error message.
14 x 0
Error peak current
If the motor current increases above the specied
limit (even in a short time-frame) the device will
switch-off.
After a switch off the controller waits for 5 seconds
then the controller attempt a start.
Arises within 60 sec. in series 5 further disconnec-
tions a nal switch off with fault indication follows.
Should no further switch off be exceeded in
60 sec. the counter will be reset.
17 x 0
Temperature alarm
Excess of the max. permissible inside tempera-
ture.
Controller switches off motor. Automatic restarting
after cooling down.
Check installation of the device and cooling of the
controller.
20 x 0
Communication fault
MODBUS communication interrupted
see description MODBUS communication
* Relays K1 programmed function at factory (Fault indication not inverted)
0 Relays de-energized
1 Relays pulled up
Assembly instructions ECblue BASIC-MODBUS, ECblue BASIC Diagnostics / Faults
L-BAL-F078D-GB 1939 Index 003 Part.-No.
64/78
7.3 Configuration of speed control
See information in manual from Ziehl Abegg. The name of the manual is L-BAL-F078–D-GB