Geniox User Manual Hygienic air handling unit

Table Of Contents
4-2
| Speed control for rotary heat exchanger
Number of red flashes in series Value
1
Output current limit
2
Over voltage
3
Under voltage
4
Failure in the controller
5
Communication failure
Restart of rotor:
Switch off power and switch on power again
or
Press the test button inside the cabinet
Table 3 Test of motor by checking the resistance in all 3 vindings
Motor sizes
Ohm
90TYD-S214-M 40Ω
120TYD-S214-M 18Ω
120TYD-S214-L 10Ω
Setting of constant speed:
Set fourth DIP switch lever in position - ON
Test:
Set fourth DIP switch lever in position ON
Press the test button
output |