Adjustment and maintenance operations |
65
Inspection door is installed in the air handling unit for easy access to removal of the droplet eliminator for cleaning out-
side the unit of the droplet eliminator on both sides. The droplet eliminator is easy removable from the air handling unit.
Lift the droplet eliminator 2 3 cm to move the underside of the eliminator over the bottom profile lower the elimi-
nator to the floor of the unit, and the eliminator is free of the upper profile. Hereby the eliminator is released for easy
withdrawal and cleaning outside the unit.
R.6.6.3 Electric heating coil
Check that the built-in safety thermostat with an automatic reset function and the overheat thermostat with manual re-
setting are fully operational.
R.6.7 Plug fans
Dust can accumulate on the fan impeller which can cause imbalance and vibrations. The fan impeller must therefore be
checked once a year and cleaned, if necessary. Anti-vibration mounts and flexible connections should be checked at
the same time. If the anti-vibration mounts are damaged in any way they must be replaced.
R.6.7.1 Motor
The motors are usually fitted with factory lubricated bearings which require no further lubrication.
R.6.8 Attenuator
During operation dust particles can accumulate on the surface of the baffles. Attenuaters that are designed for dry and
wet cleaning are fitted with baffles that can be extracted from the unit casing. Large inspection doors give access to
easily extraction of the baffles. Baffles designed for dry cleaning can be vacuum cleaned. Baffles designed for wet
cleaning can be washed down using a soft brush and soapy water. The detergent used must be non-aggressive. After
output |