Geniox User Manual Hygienic air handling unit

Table Of Contents
Adjustment and maintenance operations |
63
Drip tray with slope is not supported for the weight of a person. Do not walk or stay in the drip tray.
Demount this type of water trap regularly for careful
cleaning.
Note:
Information about disassembly, cleaning and
reassembly is available in a 2–minutes video
on YouTube.
https://youtu.be/5qMswv2c0SQ
R.6.6 Coils for heating and/or cooling cleaning
Cleaning must be carried out with the utmost care to ensure that the coil fins are not damaged. The thin fins are not
constructed for cleaning with compressed air or high pressure water.
Note:
If the coil is installed with the below valves and union fittings, the user and/or designer have prescribed in
the tender that coil and droplet eliminator if installed must be extracted for cleaning.
1. Close ball valves before disconnecting inlet and return pipes.
output |