| Adjustment and maintenance operations
Inspection door is installed in the air handling unit for easy access to removal of the droplet eliminator for cleaning out-
side the unit of the droplet eliminator on both sides. Lift the droplet eliminator 2 3 cm to move the underside of the
eliminator over the bottom profile lower the eliminator to the floor of the unit, and the eliminator is free of the upper
profile. Hereby the eliminator is released for easy withdrawal and cleaning outside the unit.
R.6.5.1 By-pass damper
The damper blades are fitted with synthetic bearings requiring no lubrication. Each damper blade is driven by a gear
drive of a temperature resistant glass fibre reinforced PA6 nylon composite. The steel rods and brass bushes do not re-
quire lubrication. Air-tightness of the dampers, when the damper motor is in the closed position, must be visually
checked once a year. The damper motor is to be adjusted if the damper does not close tightly.
R.6.5.2 Video instruction water trap cleaning and reassembly
The drip tray beneath the heat exchanger, as well as the drain and the water trap must be cleaned. Take care that there
is sufficient water in the water trap. If a droplet eliminator has been fitted, this must be checked according to the sched-
ule and cleaned if necessary.