| Adjustment and maintenance operations
R.4.3 Video instruction replace bag filters
Turn the unit off and wait for 2 minutes till unit completely stops. Used filters can be drawn out. Store the used filters
immediately in plastic bags to avoid that dust pollutes the environment. Geniox units are provided with a very corro-
sion-resistant and reliable system, where filters are slid into the air handling units in a lower and upper durable u-profile
of flexible plastic. Check the upper and lower U-profile for damage and check the flexible vertical plastic profiles as well
as the rubber profile that close between filter frame and door for damage.
Note:
Replace the profiles in case of damage.
Note:
The filters must have vertical bags.
Note:
Instructions about easy, quick and safe change of filters are displayed in a 2–minutes video. The video is
available on YouTube.
https://youtu.be/7SKylGOGNZE
The new filter bags must be pushed carefully into the U-
profile.
Note:
Prior to installation of new filters the EPDM
rubber profiles on the vertical frames must be
checked and in case of lack of flexibility and
damage the EPDM rubber profiles must be
replaced
Check that the filters are pushed to the position where
the vertical frames of the filter bags are closing fully to
the flexible vertical lists in the air handling unit for avoid-
ing any air leakage.