A label with this type of information about filters is placed
on the air handling unit.
R.4.1 Bag filters the number of filters and sizes of frames
Filters in supply air and in extract air are always the same sizes and the same numbers. See the filters in supply or ex-
tract air below.
Size of unit
Numbers and sizes of frames for bag filters (WxH)
10
1x[792x392]
11
2x[490x490]
12
1x[592x490] + 1x[490x490]
14
2x[490x592] + 1x[287x592]
16
3x[490x592]
18
2x[490x392] + 4x[592x392]
20
3x[592x592] + 3x[287x592]
22
6x[592x490] + 2x[287x490]
24
3x[592x592] + 1x[490x592] + 3x[592x490] + 1x[490x490]
27
2x[592x592] + 8x[490x592]
29
6x[592x592] + 4x[490x592]
31
5x[592x592] + 5x[490x490] + 5x[592x287]
Note:
Special sizes of filters are available from Camfil.
Dept of filter frame must be 25 mm to ensure a complete airtight sealing around the AHU filter frame
R.4.2 Panel filters the number of filters and the sizes of the frames
Size of unit
Numbers and sizes of frames for panel filters (WxHxD)
10
1x[792x392x48]
11
2x[490x392x48]
12
1x[490x490x48] + 1x[592x490x48]
14
2x[490x592x48] + 1x[287x592x48]
16
3x[490x592x48]
18
2x[490x392x48] + 4x[592x392x48]
20
3x[592x592x48] + 3x[592x287x48]
22
6x[592x490x48] + 2x[287x490x48]
24
3x[592x592x48] + 4x[490x592x48] + 1x[490x490x48]
27
2x[592x592x48] + 8x[490x592x48]
29
6x[592x592x48] + 4x[490x592x48]
31
5x[592x592x48] + 5x[592x490x48] + 5x[592x287x48]
Note: