Geniox User Manual Hygienic air handling unit

Table Of Contents
50
| Adjustment and maintenance operations
Row Item
Activity
Action if required
1 3 6 12 24
month months
12
Heat exchangers (including HRS)
12.1
Visual inspection of air-to-air
plate heat exchangers for
contamination, damage,
corrosion.
Clean, repair.
X
12.2
Visual inspection of rotary
heat exchanger for
contamination, damage,
corrosion and tightness.
Ensure tightness.
X
12.3
Visual inspection of directly
heated heat exchangers for
tightness.
Ensure tightness.
X
12.4
Heaters: Check for
contamination, damage,
corrosion and tightness
Clean and repair,
replace.
X
12.5
Coolers: Check tube bundle,
droplet eliminator and
condensate tray for
contamination, corrosion,
damage and tightness.
Clean and repair.
X
12.6
Function chek drain and drain
trap.
Clean and repair.
X
13
Underground components
13.1
Measurement of dust
concentration and
microorganisms (bacteria and
moulds) in the supply air as
compared to outdoor air and/
or reference air.
X
13.2
Check outdoor-air terminal
units for contamination and
damage.
X
13.3
Check air filters for
unacceptable contamination,
damage and odours.
X
13.4
Check air ducts for damage
X
13.5
Inspect inner air duct surface
for contamination and
condensation (using, e.g. a
camera in the absence of
suitable inspection
openings).
X