Geniox User Manual Hygienic air handling unit

Table Of Contents
Adjustment and maintenance operations |
49
Row Item
Activity
Action if required
1 3 6 12 24
month months
7
Air-terminal units
7.1
Check air-terminal units,
built-in perforated sheets,
wire mesh, or sieves for
contamination, damage and
corrosion (sample).
Clean or replace.
X
7.2
Filter fleeces Replace.
X
7.3
Sample-check air-terminal
units with indoor-air
induction and extract-air
inlets for solid deposits.
Clean.
X
7.4
Components through which
secondary air flows
Clean.
X
8
Air filters
8.1
Check for unacceptable
contamination and damage
(leaks) and odours.
Change affected air
filters.
X
8.2
Check differential pressure. Replace filter stage.
X
8.3
Maximum interval until first
filter stage is to be changed.
X
8.4
Maximum interval until
second filter stage is to be
changed.
X
9
Air ducts
9.1
Check accessible air duct
sections for damage
Repair. X
9.2
Check two or three
representative locations on
inner air duct surface for
contamination, corrosion and
condensation.
Inspect duct system at
further locations,
decide on the
necessity to clean all
(visible and not
visible) sections.
X
10
Silencers
10.1
Check silencers for
contamination, damage and
corrosion.
Repair or replace; Test
with contact slides if
necessary.
X
11 Fan
11.1
Check silencers for
contamination, damage and
corrosion.
Clean and repair,
check water drain.
X
output |