Geniox User Manual Hygienic air handling unit
Table Of Contents
- A Manufacturer
- B Name of machines
- C Declaration of Conformity - example
- D General descriptions, dangers and warnings
- D.1 Overview via pictograms on the inspection side of the unit
- D.2 Data about the unit according to cards and labels in and on the unit
- D.2.1 Example of CE labelling and Machine card with unique data on every unit
- D.2.2 Label with data about the cabinet — example.
- D.2.3 Flowchart – example of the label placed on or with the cabinet
- D.2.4 Symbols in the flowchart and explanation about the symbols
- D.2.5 Example of label placed on or with the cabinet – Terminal plan for external components
- D.2.6 Control board for Systemair Access control system
- D.3 The control panel for the control system.
- D.4 Dimensions of the units
- D.5 Ordinary automatically operation – only manual operation by new parameters
- E Drawings, diagrams, guides and instructions for the use, maintenance and repair
- F Employees in charge of operation/control/maintenance
- G Intended use and range of applications
- H Unintended use and misuse – inappropriate applications for the machine
- I Instructions for unloading on the site as well as installation and connection
- I.1 Unloading on the site
- I.1.1 Handling methods
- I.1.2 Unloading by forklift truck
- I.1.3 Unloading by crane
- I.1.4 Transport of unit without base frame on the site
- I.1.5 Lifting a unit with straps
- I.1.6 Lifting a unit with installed brackets on the base frame for lifting.
- I.1.7 Lifting a unit without base frame and legs but with installed brackets for lifting.
- I.1.8 Handling a unit with holes in base frame for forks
- I.1.9 Roof unit with PVC, flat sheet steel plates or bitumen
- I.1.10 Roof unit with steel roof
- I.1.11 Long-term storage before installation — outdoor or in not heated and humid building
- I.1.12 Tilt less than 30˚ during transportation of the section with heat pump
- I.1.13 Transport and pre-installation storage of rotary heat exchanger — always in vertical position
- I.2 Installation - mechanical
- I.2.1 Free area in front of and above the unit
- I.2.2 Supporting surface
- I.2.3 Adjustable feet under legs or base frame and transport of sections
- I.2.4 Base frames for outdoor units
- I.2.5 Outdoor units — support under the base frame of the unit
- I.2.6 Installation on the site of unit sections.
- I.2.7 Joining the sections
- I.2.8 Risk of stack effect by vertical ducts and wind pressure on louvers
- I.2.9 Fitting the ductwork
- I.2.10 Refitting of safety guards
- I.2.11 Lock the doors by using the key
- I.3 Installation - electrical
- I.3.1 Video instruction and overview
- I.3.2 Wiring diagrams
- I.3.3 Installation of mains power supply
- I.3.4 Electrical connection of components and functions
- I.3.5 Fans — cable connections with plugs for easy demounting of fans
- I.3.6 Filters — differential pressure gauge for each filter stage
- I.3.7 Lock the doors by using the key
- I.4 Installation – pipes for water – hot and chilled, valves and drains
- I.4.1 Description
- I.4.2 Pipe connections
- I.4.3 Pipes and cables must not obstruct opening of doors and extraction of components from the unit
- I.4.4 Pipe connections to coils that must be extracted for cleaning
- I.4.5 Droplet eliminator — access to removal and cleaning
- I.4.6 Draining condensate water
- I.4.7 Video instruction — draining condensate water from heat exchanger
- I.4.8 Draining condensate water from cooling coil
- I.4.9 A maximum of 90% relative humidity must not be exceed before second filter stage or silencers
- I.4.10 Clean and disinfect the interior of the unit as second last action for the installer before start-up and hand over of the unit to the user
- I.4.11 Install delivered filters in the cleaned unit as last action for the installer before start-up and hand over of the unit to the user
- I.1 Unloading on the site
- J Installation and assembly instructions for reduction of noise and vibration emissions
- K Start-up, adjustments, use, commissioning and unit in out of regular operation for several months
- K.1 Print-outs on paper
- K.2 Documentation is available for download
- K.3 Start-up by installer
- K.4 Video instructions about adjustments and use via the control panel
- K.5 Description of the control system functions
- K.5.1 Remote control
- K.5.2 Extended operation and external start/stop (for example by presence detectors)
- K.5.3 Valve and valve motor for heating coil
- K.5.4 Valve and valve motor for cooling coil
- K.5.5 DX cooling
- K.5.6 Circulation pump, heating
- K.5.7 Fire alarm function
- K.5.8 Electrical heater battery
- K.5.9 Speed control of fans
- K.5.10 Cabinet
- K.5.11 Temperature sensors
- K.5.12 Damper motors
- K.5.13 Filter guards
- K.5.14 Room temperature sensors
- K.5.15 Frost protection
- K.5.16 Systemair Control Panel - NaviPad
- K.5.17 Cooling recovery
- K.5.18 Free cooling
- K.5.19 Alarm signal
- K.5.20 Heat recovery
- K.5.21 Frost protection – plate heat exchanger
- K.6 Commissioning
- K.7 Accurate measuring of SFP (Specific Fan Power)
- K.8 Unit in not in regular operation for several months
- L Information about the residual risks
- M Instructions on the protective measures during repair and maintenance
- N The essential characteristics of tools which may be fitted to the machinery
- O The conditions of stability during use, transportation, assembly, dismantling when out of service
- P Instructions for machinery where these are regularly to be transported
- Q The operating method to be followed in the event of breakdown. Safe restart.
- R Adjustment and maintenance operations
- R.1 Shutdown of the unit to a safe state
- R.2 Unlock and lock the doors by using the key
- R.3 Checklist with schedules about cleaning and repair
- R.4 Filters – always replace filters with new filters with the same characteristics as original filters to maintain SFP value
- R.4.1 Bag filters – the number of filters and sizes of frames
- R.4.2 Panel filters – the number of filters and the sizes of the frames
- R.4.3 Video instruction — replace bag filters
- R.4.4 For hygienic units replaced U-profiles for filters must comply with ISO 846 — see spare part article number
- R.4.5 Panel filters
- R.5 Changing the Internal Battery in the controller
- R.6 Functions to maintain
- R.6.1 The unit
- R.6.2 For hygienic units replaced door gasket and sealing lists must comply with ISO 846 — see spare part article numbers
- R.6.3 Dampers
- R.6.4 Rotary heat exchanger
- R.6.5 Cross flow and counter flow plate heat exchanger — cleaning
- R.6.6 Coils for heating and/or cooling — cleaning
- R.6.7 Plug fans
- R.6.8 Attenuator
- R.6.9 Outdoor air section
- R.6.10 Heat pump unit
- S Instructions to enable adjustment and maintenance safely
- T The specifications of the spare parts to be used, when these affect the health and safety of operators
- U Information on airborne noise emissions exceeding 70 dB(A)
- Annex 1 Declaration of conformity with production number (in separate cover)
- Annex 2 Technical data – unique data for every unit (in separate cover)
- Annex 3 Spare part list (in separate cover — is only available on demand)
- Annex 4 Speed control for rotary heat exchanger
- Annex 5 Reversible heat pump unit (in separate cover, if heat pump was delivered)
- Annex 6 Menu for internal controller in the heat pump unit (in separate cover, if heat pump was delivered)
- Annex 7 Connection of EC fan motor, diagnostics/faults and configuration of speed control
- Annex 8 Commissioning protocol – proposal (in separate cover)
- Annex 9 Report with data from final functional test on the Systemair factory (in separate cover)
- Annex 10 Short description of main components in the control system
- Annex 11 Wiring diagram (in separate cover)
44
| Instructions on the protective measures during repair and maintenance
Claim for reduction of danger:
• Installer and user must be aware of the fact that lightning makes a risk that requires installation of overvoltage pro-
tection devices to lead the lightning overvoltage to an earth lead on a safe way. The need for overvoltage protection
devices depend on where the unit is placed in and on the building.
• Installer and user must take care of this according to local statutory requirements. Overvoltage protection devices
are also described in chapter I.3.3.2 of this manual
M Instructions on the protective measures during repair and maintenance
Use the below-mentioned personal protective equipment for maintenance:
• Cut-resistant gloves for protection against injury from sharp metal plate edges. Use CE-marked gloves for this
purpose.
• Helmet
• Particulate respirator – maintenance free including foam face-seal and adjustable pre-threaded headbands – for re-
placing filters.
• Padlock for locking the automatic circuit breakers in off position
• Permanent magnet motor. The shaft must be blocked during repairs and maintenance of the electric system (the
motor generates electricity by rotation – for example that the wind and thermic drives the fan/motor).
• Lighting inside the units. According to the latest interpretations of the Machinery Directive by the authorities suffi-
cient lighting inside the units is mandatory.
• Tools to block the impeller during repairs and maintenance if stack effect – also called chimney effect – in the ducts
create airflows that drives the impellers by turned off motors
N The essential characteristics of tools which may be fitted to the machinery
The subject in the Machinery Directive about tools on the machine does not exist for the Geniox air handling units, be-
cause those tools does not exist.
O The conditions of stability during use, transportation, assembly, dismantling
when out of service
The unit must always be handled in an upright position. Never tilt any section more than 15 degrees. If sections must
be tilted more than 15 degrees, sections with fans or rotating exchangers that can be drawn out for service must be se-
cured carefully.
During transportation, installation, dismantling or other handling, it must be secured that all components in the unit are
properly fastened and with additional attention to the control of anti-vibration mounts under the fans that they are un-
damaged. The mounting and smooth running of the fans must be controlled and handled with great care.
O.1 Installed reliable to avoid units to be tilted or moved by storm
Units installed on roofs and other places with the risk of heavy winds must be installed reliable to avoid that they can
be tilted or moved by the any storm. The base frame is provided with holes that are intended for fastening by sufficient
bolts and fittings supplied by the installer.
O.2 Transport of section with heat pump unit
Warning
During transportation, the unit section – Geniox — HP must always be in the upright position or tilted less
than 30˚. If it is necessary to tilt the unit more than 30˚, the suction pipe of the compressor must point
upwards to prevent the escape of oil from the compressor sump.
O.3 Disposal of the heat pump system - type Geniox - HP
Prior to the disposal of the Geniox — HP unit section, the refrigerant in the heat pump system must be drained off by a
skilled technician from a certified company. After correct evacuation of the refrigerant, the disposal of the Geniox — HP
unit section is similar to the disposal of the rest of the air handling unit.
output |