K.7 Accurate measuring of SFP (Specific Fan Power)
When the cabinet is installed behind the inspection door
for the supply air fan, the displayed cover called service
door in the inspection door is removed, there is no leak-
age of air flow, and the true power consumption can be
measured by connection of an instrument to the termi-
nals in the cabinet.
Measure the ampere by the clamps as show and measure
the volts on the terminals L1, L2 and L3 as shown.