Geniox User Manual Hygienic air handling unit
Table Of Contents
- A Manufacturer
- B Name of machines
- C Declaration of Conformity - example
- D General descriptions, dangers and warnings
- D.1 Overview via pictograms on the inspection side of the unit
- D.2 Data about the unit according to cards and labels in and on the unit
- D.2.1 Example of CE labelling and Machine card with unique data on every unit
- D.2.2 Label with data about the cabinet — example.
- D.2.3 Flowchart – example of the label placed on or with the cabinet
- D.2.4 Symbols in the flowchart and explanation about the symbols
- D.2.5 Example of label placed on or with the cabinet – Terminal plan for external components
- D.2.6 Control board for Systemair Access control system
- D.3 The control panel for the control system.
- D.4 Dimensions of the units
- D.5 Ordinary automatically operation – only manual operation by new parameters
- E Drawings, diagrams, guides and instructions for the use, maintenance and repair
- F Employees in charge of operation/control/maintenance
- G Intended use and range of applications
- H Unintended use and misuse – inappropriate applications for the machine
- I Instructions for unloading on the site as well as installation and connection
- I.1 Unloading on the site
- I.1.1 Handling methods
- I.1.2 Unloading by forklift truck
- I.1.3 Unloading by crane
- I.1.4 Transport of unit without base frame on the site
- I.1.5 Lifting a unit with straps
- I.1.6 Lifting a unit with installed brackets on the base frame for lifting.
- I.1.7 Lifting a unit without base frame and legs but with installed brackets for lifting.
- I.1.8 Handling a unit with holes in base frame for forks
- I.1.9 Roof unit with PVC, flat sheet steel plates or bitumen
- I.1.10 Roof unit with steel roof
- I.1.11 Long-term storage before installation — outdoor or in not heated and humid building
- I.1.12 Tilt less than 30˚ during transportation of the section with heat pump
- I.1.13 Transport and pre-installation storage of rotary heat exchanger — always in vertical position
- I.2 Installation - mechanical
- I.2.1 Free area in front of and above the unit
- I.2.2 Supporting surface
- I.2.3 Adjustable feet under legs or base frame and transport of sections
- I.2.4 Base frames for outdoor units
- I.2.5 Outdoor units — support under the base frame of the unit
- I.2.6 Installation on the site of unit sections.
- I.2.7 Joining the sections
- I.2.8 Risk of stack effect by vertical ducts and wind pressure on louvers
- I.2.9 Fitting the ductwork
- I.2.10 Refitting of safety guards
- I.2.11 Lock the doors by using the key
- I.3 Installation - electrical
- I.3.1 Video instruction and overview
- I.3.2 Wiring diagrams
- I.3.3 Installation of mains power supply
- I.3.4 Electrical connection of components and functions
- I.3.5 Fans — cable connections with plugs for easy demounting of fans
- I.3.6 Filters — differential pressure gauge for each filter stage
- I.3.7 Lock the doors by using the key
- I.4 Installation – pipes for water – hot and chilled, valves and drains
- I.4.1 Description
- I.4.2 Pipe connections
- I.4.3 Pipes and cables must not obstruct opening of doors and extraction of components from the unit
- I.4.4 Pipe connections to coils that must be extracted for cleaning
- I.4.5 Droplet eliminator — access to removal and cleaning
- I.4.6 Draining condensate water
- I.4.7 Video instruction — draining condensate water from heat exchanger
- I.4.8 Draining condensate water from cooling coil
- I.4.9 A maximum of 90% relative humidity must not be exceed before second filter stage or silencers
- I.4.10 Clean and disinfect the interior of the unit as second last action for the installer before start-up and hand over of the unit to the user
- I.4.11 Install delivered filters in the cleaned unit as last action for the installer before start-up and hand over of the unit to the user
- I.1 Unloading on the site
- J Installation and assembly instructions for reduction of noise and vibration emissions
- K Start-up, adjustments, use, commissioning and unit in out of regular operation for several months
- K.1 Print-outs on paper
- K.2 Documentation is available for download
- K.3 Start-up by installer
- K.4 Video instructions about adjustments and use via the control panel
- K.5 Description of the control system functions
- K.5.1 Remote control
- K.5.2 Extended operation and external start/stop (for example by presence detectors)
- K.5.3 Valve and valve motor for heating coil
- K.5.4 Valve and valve motor for cooling coil
- K.5.5 DX cooling
- K.5.6 Circulation pump, heating
- K.5.7 Fire alarm function
- K.5.8 Electrical heater battery
- K.5.9 Speed control of fans
- K.5.10 Cabinet
- K.5.11 Temperature sensors
- K.5.12 Damper motors
- K.5.13 Filter guards
- K.5.14 Room temperature sensors
- K.5.15 Frost protection
- K.5.16 Systemair Control Panel - NaviPad
- K.5.17 Cooling recovery
- K.5.18 Free cooling
- K.5.19 Alarm signal
- K.5.20 Heat recovery
- K.5.21 Frost protection – plate heat exchanger
- K.6 Commissioning
- K.7 Accurate measuring of SFP (Specific Fan Power)
- K.8 Unit in not in regular operation for several months
- L Information about the residual risks
- M Instructions on the protective measures during repair and maintenance
- N The essential characteristics of tools which may be fitted to the machinery
- O The conditions of stability during use, transportation, assembly, dismantling when out of service
- P Instructions for machinery where these are regularly to be transported
- Q The operating method to be followed in the event of breakdown. Safe restart.
- R Adjustment and maintenance operations
- R.1 Shutdown of the unit to a safe state
- R.2 Unlock and lock the doors by using the key
- R.3 Checklist with schedules about cleaning and repair
- R.4 Filters – always replace filters with new filters with the same characteristics as original filters to maintain SFP value
- R.4.1 Bag filters – the number of filters and sizes of frames
- R.4.2 Panel filters – the number of filters and the sizes of the frames
- R.4.3 Video instruction — replace bag filters
- R.4.4 For hygienic units replaced U-profiles for filters must comply with ISO 846 — see spare part article number
- R.4.5 Panel filters
- R.5 Changing the Internal Battery in the controller
- R.6 Functions to maintain
- R.6.1 The unit
- R.6.2 For hygienic units replaced door gasket and sealing lists must comply with ISO 846 — see spare part article numbers
- R.6.3 Dampers
- R.6.4 Rotary heat exchanger
- R.6.5 Cross flow and counter flow plate heat exchanger — cleaning
- R.6.6 Coils for heating and/or cooling — cleaning
- R.6.7 Plug fans
- R.6.8 Attenuator
- R.6.9 Outdoor air section
- R.6.10 Heat pump unit
- S Instructions to enable adjustment and maintenance safely
- T The specifications of the spare parts to be used, when these affect the health and safety of operators
- U Information on airborne noise emissions exceeding 70 dB(A)
- Annex 1 Declaration of conformity with production number (in separate cover)
- Annex 2 Technical data – unique data for every unit (in separate cover)
- Annex 3 Spare part list (in separate cover — is only available on demand)
- Annex 4 Speed control for rotary heat exchanger
- Annex 5 Reversible heat pump unit (in separate cover, if heat pump was delivered)
- Annex 6 Menu for internal controller in the heat pump unit (in separate cover, if heat pump was delivered)
- Annex 7 Connection of EC fan motor, diagnostics/faults and configuration of speed control
- Annex 8 Commissioning protocol – proposal (in separate cover)
- Annex 9 Report with data from final functional test on the Systemair factory (in separate cover)
- Annex 10 Short description of main components in the control system
- Annex 11 Wiring diagram (in separate cover)
38
| Start-up, adjustments, use, commissioning and unit in out of regular operation for several months
K.5.13 Filter guards
Filter guard over pre-filter and primary filter installed and connected to the controller for display of alarm when the me-
chanically set limit is exceeded. Filter alarm will be displayed on the Systemair Control Panel.
K.5.14 Room temperature sensors
One or two external room temperature sensors are available. The cabinet has been prepared with additional terminals
for connection of the room temperature sensors. The sensors are delivered without cable. The controller calculates an
average of the value from the 2 sensors as input for the control.
K.5.15 Frost protection
For the frost protection of the heating coil, the water temperature in the coil is transmitted to the controller by a tem-
perature sensor in a water return circuit of the coil. The controller always generates a signal to the valve motor that
keeps a sufficient flow of hot water to protect the coil against frost. This frost protection is also activated when the run-
ning mode is “off”.
If the water temperature falls below the set point temperature the fans stop, the dampers close, and an alarm is
activated.
From Systemair every heating coil for hot water is provided with a little pipe at the collection pipe for the return water.
This little pipe is prepared for the installation of the above mentioned temperature sensor for the transmission of the re-
turn water temperature to the controller.
K.5.16 Systemair Control Panel - NaviPad
The separate cable-connected (3m) hand terminal with touch screen — the NaviPad is always necessary for the normal
handling and programming, because the main controller — Access — is without display and buttons.
K.5.17 Cooling recovery
If the extract air temperature is lower than the outdoor air temperature, and there is a cooling demand in the rooms,
the cooling recovery will be activated by reversing the heat exchanger signal. The signal is increased to the cooling re-
covery by increasing cooling demand.
K.5.18 Free cooling
A temperature sensor has been installed inside the unit in the outdoor air entrance. If the outdoor temperature after
midnight is below the room temperature set point and the actual average room temperature is above the set point
temperature, the fans start during the summer to cool down the building during night hours.
K.5.19 Alarm signal
By alarm there are 24 V DC on terminals in the cabinet. Lamps and cables are not available from Systemair.
K.5.20 Heat recovery
The heat recovery capacity is controlled by modulating speed of the rotor.
K.5.21 Frost protection – plate heat exchanger
Signals from a temperature sensor mounted in the airflow after the plate heat exchanger are transmitted to the control-
ler for frost protection of the plate heat exchanger.
K.6 Commissioning
When the installer has completed the installation and wants to hand over the finished installation to his customer for
payment the commissioning protocol can be the written receipt for the full ended job. Fill in the blank spaces and sign
the proposed commissioning protocol that is Annex 8, or fill in the Word-file with a Commissioning Protocol that is avail-
able from your local Systemair office.
output |