Geniox User Manual Hygienic air handling unit
Table Of Contents
- A Manufacturer
- B Name of machines
- C Declaration of Conformity - example
- D General descriptions, dangers and warnings
- D.1 Overview via pictograms on the inspection side of the unit
- D.2 Data about the unit according to cards and labels in and on the unit
- D.2.1 Example of CE labelling and Machine card with unique data on every unit
- D.2.2 Label with data about the cabinet — example.
- D.2.3 Flowchart – example of the label placed on or with the cabinet
- D.2.4 Symbols in the flowchart and explanation about the symbols
- D.2.5 Example of label placed on or with the cabinet – Terminal plan for external components
- D.2.6 Control board for Systemair Access control system
- D.3 The control panel for the control system.
- D.4 Dimensions of the units
- D.5 Ordinary automatically operation – only manual operation by new parameters
- E Drawings, diagrams, guides and instructions for the use, maintenance and repair
- F Employees in charge of operation/control/maintenance
- G Intended use and range of applications
- H Unintended use and misuse – inappropriate applications for the machine
- I Instructions for unloading on the site as well as installation and connection
- I.1 Unloading on the site
- I.1.1 Handling methods
- I.1.2 Unloading by forklift truck
- I.1.3 Unloading by crane
- I.1.4 Transport of unit without base frame on the site
- I.1.5 Lifting a unit with straps
- I.1.6 Lifting a unit with installed brackets on the base frame for lifting.
- I.1.7 Lifting a unit without base frame and legs but with installed brackets for lifting.
- I.1.8 Handling a unit with holes in base frame for forks
- I.1.9 Roof unit with PVC, flat sheet steel plates or bitumen
- I.1.10 Roof unit with steel roof
- I.1.11 Long-term storage before installation — outdoor or in not heated and humid building
- I.1.12 Tilt less than 30˚ during transportation of the section with heat pump
- I.1.13 Transport and pre-installation storage of rotary heat exchanger — always in vertical position
- I.2 Installation - mechanical
- I.2.1 Free area in front of and above the unit
- I.2.2 Supporting surface
- I.2.3 Adjustable feet under legs or base frame and transport of sections
- I.2.4 Base frames for outdoor units
- I.2.5 Outdoor units — support under the base frame of the unit
- I.2.6 Installation on the site of unit sections.
- I.2.7 Joining the sections
- I.2.8 Risk of stack effect by vertical ducts and wind pressure on louvers
- I.2.9 Fitting the ductwork
- I.2.10 Refitting of safety guards
- I.2.11 Lock the doors by using the key
- I.3 Installation - electrical
- I.3.1 Video instruction and overview
- I.3.2 Wiring diagrams
- I.3.3 Installation of mains power supply
- I.3.4 Electrical connection of components and functions
- I.3.5 Fans — cable connections with plugs for easy demounting of fans
- I.3.6 Filters — differential pressure gauge for each filter stage
- I.3.7 Lock the doors by using the key
- I.4 Installation – pipes for water – hot and chilled, valves and drains
- I.4.1 Description
- I.4.2 Pipe connections
- I.4.3 Pipes and cables must not obstruct opening of doors and extraction of components from the unit
- I.4.4 Pipe connections to coils that must be extracted for cleaning
- I.4.5 Droplet eliminator — access to removal and cleaning
- I.4.6 Draining condensate water
- I.4.7 Video instruction — draining condensate water from heat exchanger
- I.4.8 Draining condensate water from cooling coil
- I.4.9 A maximum of 90% relative humidity must not be exceed before second filter stage or silencers
- I.4.10 Clean and disinfect the interior of the unit as second last action for the installer before start-up and hand over of the unit to the user
- I.4.11 Install delivered filters in the cleaned unit as last action for the installer before start-up and hand over of the unit to the user
- I.1 Unloading on the site
- J Installation and assembly instructions for reduction of noise and vibration emissions
- K Start-up, adjustments, use, commissioning and unit in out of regular operation for several months
- K.1 Print-outs on paper
- K.2 Documentation is available for download
- K.3 Start-up by installer
- K.4 Video instructions about adjustments and use via the control panel
- K.5 Description of the control system functions
- K.5.1 Remote control
- K.5.2 Extended operation and external start/stop (for example by presence detectors)
- K.5.3 Valve and valve motor for heating coil
- K.5.4 Valve and valve motor for cooling coil
- K.5.5 DX cooling
- K.5.6 Circulation pump, heating
- K.5.7 Fire alarm function
- K.5.8 Electrical heater battery
- K.5.9 Speed control of fans
- K.5.10 Cabinet
- K.5.11 Temperature sensors
- K.5.12 Damper motors
- K.5.13 Filter guards
- K.5.14 Room temperature sensors
- K.5.15 Frost protection
- K.5.16 Systemair Control Panel - NaviPad
- K.5.17 Cooling recovery
- K.5.18 Free cooling
- K.5.19 Alarm signal
- K.5.20 Heat recovery
- K.5.21 Frost protection – plate heat exchanger
- K.6 Commissioning
- K.7 Accurate measuring of SFP (Specific Fan Power)
- K.8 Unit in not in regular operation for several months
- L Information about the residual risks
- M Instructions on the protective measures during repair and maintenance
- N The essential characteristics of tools which may be fitted to the machinery
- O The conditions of stability during use, transportation, assembly, dismantling when out of service
- P Instructions for machinery where these are regularly to be transported
- Q The operating method to be followed in the event of breakdown. Safe restart.
- R Adjustment and maintenance operations
- R.1 Shutdown of the unit to a safe state
- R.2 Unlock and lock the doors by using the key
- R.3 Checklist with schedules about cleaning and repair
- R.4 Filters – always replace filters with new filters with the same characteristics as original filters to maintain SFP value
- R.4.1 Bag filters – the number of filters and sizes of frames
- R.4.2 Panel filters – the number of filters and the sizes of the frames
- R.4.3 Video instruction — replace bag filters
- R.4.4 For hygienic units replaced U-profiles for filters must comply with ISO 846 — see spare part article number
- R.4.5 Panel filters
- R.5 Changing the Internal Battery in the controller
- R.6 Functions to maintain
- R.6.1 The unit
- R.6.2 For hygienic units replaced door gasket and sealing lists must comply with ISO 846 — see spare part article numbers
- R.6.3 Dampers
- R.6.4 Rotary heat exchanger
- R.6.5 Cross flow and counter flow plate heat exchanger — cleaning
- R.6.6 Coils for heating and/or cooling — cleaning
- R.6.7 Plug fans
- R.6.8 Attenuator
- R.6.9 Outdoor air section
- R.6.10 Heat pump unit
- S Instructions to enable adjustment and maintenance safely
- T The specifications of the spare parts to be used, when these affect the health and safety of operators
- U Information on airborne noise emissions exceeding 70 dB(A)
- Annex 1 Declaration of conformity with production number (in separate cover)
- Annex 2 Technical data – unique data for every unit (in separate cover)
- Annex 3 Spare part list (in separate cover — is only available on demand)
- Annex 4 Speed control for rotary heat exchanger
- Annex 5 Reversible heat pump unit (in separate cover, if heat pump was delivered)
- Annex 6 Menu for internal controller in the heat pump unit (in separate cover, if heat pump was delivered)
- Annex 7 Connection of EC fan motor, diagnostics/faults and configuration of speed control
- Annex 8 Commissioning protocol – proposal (in separate cover)
- Annex 9 Report with data from final functional test on the Systemair factory (in separate cover)
- Annex 10 Short description of main components in the control system
- Annex 11 Wiring diagram (in separate cover)
32
| Instructions for unloading on the site as well as installation and connection
This type of water trap for sections with negative pres-
sure and a ball that is sucked down into its seat for block-
age of air flow into the section is available from
Systemair. The above-mentioned heights — H1 and H2 —
also apply to this type of water trap. The great advantage
of this type of water trap for sections with negative pres-
sure is that this type does not require water at the bottom
to close for air flow backwards into the section. Conden-
sate water will escape through this type of water trap —
even after long periods without any water to close for air
flow backwards through the trap.
This water trap is optional and must be ordered sepa-
rately. Installation of water trap is not included.
The water trap in this picture has the delivered standard
length of H1 of 150 mm and with the adjustable length of
H2 adjusted to 55 mm, this set-up allows water to flow
out at a negative pressure of 750 Pa, because the closing
level that is H1 minus H2 is 95 mm and with 75 mm cor-
responding to the negative pressure lifting the water 75
mm and an excess height of 20 mm that enables the
water to lift the ball and to flow out through the water
trap into the sewage system..
H1 must be shortened on the site by the installer —
sometimes to only 100 mm — because the height of the
low version of the base frame is only 118 mm. The ad-
justable length of H2 must be reduced to the minimum of
40 mm. According to the values in the above table, this
allows Water to flow out at a negative pressure up to 500
Pa because the closing level that is H1 minus H2 is 60
mm with 50 mm corresponding to the negative pressure
lifting the water 50 mm and an excess height of 10 mm
that enables the water to lift the ball and to flow out
through the water trap into the sewage system.
To avoid freeze ups and frost bursts of water trap and
pipes, sufficient insulation is recommended and installa-
tion of heating between the insulation and water trap/
pipes could even be necessary (insulation, heating and
controller for the heating are not delivered by Systemair).
The insulation must be easy to remove above the cap, be-
cause the ball and the seat for the ball must be cleaned
regularly to allow the ball to close air-tight to the seat.
Caution
The installer at the building site must build a pipe system between the water trap and the sewage system of
the building where the pipe from the water trap ends a few millimetres in the open atmosphere over a grate
of the sewage system to avoid any backflow of water through the water trap to to the airflow in the unit.
I.4.8 Draining condensate water from cooling coil
If the cooling coil and the drip tray are placed in the section where negative pressure (underpressure) occurs, the clos-
ing level of the water trap must be estimated correctly. See the above-mentioned information in I.4.7 Video instruction
— draining condensate water from heat exchanger. If the cooling coil and the drip tray are placed in the unit where
output |