I.2.9 Fitting the ductwork
Flexible duct connections between AHU and ductwork must always be installed. Be sure that flexible duct connections
are almost fully stretched. (Flexible connections are ordered as accessories and they are placed inside the unit).
Rigid duct connection at the Geniox unit is available with 20 mm or 30 mm flange for LS profile and screw clamps.
Please check the order confirmation or the data in the annex 2 concerning the size of the flange 20 mm or 30 mm.
Furthermore the rigid duct connection is always with a
8,5 mm hole in each corner of the flange.
Use 8 mm bolt with nut in each corner and a sufficient
number of screw clamps with a distance between screw
clamps that not exceeds 300 mm to hold the duct,
damper, coil or attenuator tight together
Size of duct connections at the 12 sizes of Geniox units
Size of unit Width in mm Height in mm
10 1000 400
11 1100 450
12 1200 500
14 1400 600
16 1600 700
18 1800 800
20 2000 900
22 2200 1000
24 2400 1100
27 2700 1200
29 2900 1300
31 3100 1400
I.2.10 Refitting of safety guards
The guard is a safety guard installed inside the door. Note! The safety guard shown on the illustration below is option-
al from Systemair and must be ordered separately. According to Machinery Directive guidelines, tools are necessary
for the removal of the guard. If the guard has been demounted during the installation on the site, the guard must be re-
fitted before startup of the unit.
If the optional guard from Systemair has not been ordered, the installer, that starts-up the unit, must make and install a
guard, where a guard is demanded according to Machinery Directive guidelines.