Geniox User Manual Hygienic air handling unit

Table Of Contents
22
| Instructions for unloading on the site as well as installation and connection
Bracket inside a section. A similar bracket is installed in
the next section. This is the bracket in the Geniox sizes 10
and 18
Press the sections hard together so that the rubber pro-
files are so flat that the iron frames of the two sections
are joined. Strap with tensioner is suitable for pressing
the sections hard together.. Note! To avoid any load and
stress on the vertical profiles the strap must be carefully
placed on the bottom profiles of the unit.
The sections must then be locked permanently together
with 8 mm bolts. Nut with threat is installed from the fac-
tory in one of the brackets
Note! Do not pull the sections together by tensioning
the 8 mm bolts. Use the strap for this purpose.
Brackets inside a section. Similar brackets are installed in
the next section. These are the brackets in the Geniox
sizes 20
Press the sections hard together so that the rubber pro-
files are so flat that the iron frames of the two sections
are joined. Strap with tensioner is suitable for pressing
the sections hard together.. Note! Do not place the strap
on the vertical profiles. To avoid any load and stress on
the profiles the strap must be carefully placed on the
bottom profiles of the unit.
The sections must then be locked permanently together
with 8 mm bolts. Nut with threat is installed from the fac-
tory in one of the brackets
Note! Do not pull the sections together by tensioning
the 8 mm bolts. Use a strap for this pupose.
I.2.8 Risk of stack effect by vertical ducts and wind pressure on louvers
Important
The Systemair air handling units can be ordered and delivered without dampers, and the installer/user must
check that duct systems with the described risk of stack effect (chimney effect) will be provided with
dampers and spring return motors.
On special occasions stack effect also called chimney effect in the ducts create airflows that drives the impellers by
turned off motors.
A rotating impeller is a potential hazard during cleaning and maintenance of the unit. Eliminate this airflow by dampers
with spring return motors for automatic closing of the dampers - even by power failure.
output |