| Adjustment and maintenance operations
Q.6.7.1 Heating coil
Check that the frost protection system is fully operational. A coil may burst due to frost if the frost protection system is
not operational.
Q.6.7.2 Cooling coil
Once a year clean the drip tray beneath the cooling coil, as well as the drain and the water trap. Take care that there is
sufficient water in the water trap. If a droplet eliminator has been fitted to the cooling coil, this must be checked once a
year and cleaned if necessary.
Droplet eliminator must be checked once a year and cleaned if necessary.