Geniox user manual

Table Of Contents
56
| Adjustment and maintenance operations
Q.6.4 Cross flow and counter flow exchanger
Note:
Once a year the edges of the heat exchanger plates are to be checked for cleanliness and damage.
If there is dust on the edges of the plates, remove it with a soft brush. The thin plates are not constructed for cleaning
with compressed air or water.
Q.6.4.1 By-pass damper
The damper blades are fitted with synthetic bearings requiring no lubrication. Each damper blade is driven by a gear
drive of a temperature resistant glass fibre reinforced PA6 nylon composite. The steel rods and brass bushes do not re-
quire lubrication. Air-tightness of the dampers, when the damper motor is in the closed position, must be visually
checked once a year. The damper motor is to be adjusted if the damper does not close tightly.
Q.6.4.2 Condensate water drain
At least once a year the drip tray beneath the heat exchanger, as well as the drain and the water trap must be cleaned.
Take care that there is sufficient water in the water trap. If a droplet eliminator has been fitted, this must be checked
once a year and cleaned if necessary.
Note:
Instructions about easy, quick and safe cleaning of water trap is displayed in a 2–minutes video. The video is
available on YouTube.
https://youtu.be/5qMswv2c0SQ
output | 11