| Adjustment and maintenance operations
Q.3 Recommended maintenance intervals
Function Maintenance
Number
per year
Unit casing
Cleaning of the unit casing.
1
Control of rubber seals on doors and between sections.
1
Filters Change on demand by alarm and always minimum twice a year.
2
Control of rubber seals. Control of the system on Geniox10 Geniox31.
2
Fans
Cleaning of all parts.
1
Check motors and bearings
1
Check that the impellers are rotating without dissonance.
1
Check that anti-vibration mounts are intact.
1
Check that the unit is operating without vibrations after the cleaning,
overhaul and maintenance.
1
Rotary heat exchanger Check that leakage is insignificant. By significant leakage brush seals must
be replaced.
1
Check that the rotor can turn freely and easily manually with a hand when
the belt is removed from the drive
1
Check that dirt accumulation is insignificant. The rotor can only be cleaned by
gentle vacuum cleaning.
1
Check drive belt, motor and the speed control system. Check and repair
immediately by alarm for malfunction.
1
Plate heat exchanger Check bypass function and sequence for de-icing. Check and repair
immediately by alarm for malfunction.
1
Run-around heat
exchanger
Check the exchanger function and test the frost protection. The glycol must
be without additives and auto glycol must not be used. Check and repair
immediately by alarm for malfunction.
1
Dampers
Test the operation.
1
Visual inspection of seals and tightness when closed.
1
Hot water coil Check the dirt accumulation and clean, if needed.
1
Bleeding, if needed.
1
Test of frost protection sequence
1
Test of circulation pump
1
Electric heating coil Check dirt accumulation and clean, if needed.
1
Test the function of the system with the fuses for the safety.
1
Cooling coil Check dirt accumulation and clean, if needed.
1
Test the frost protection (glycol)
1
Heat pump unit
Mandatory annual control of the heat pump system. Must be done by
certified technician from a certified company.
1
Condensate drain Cleaning of tray, water trap and outlet. Check the electrical heating between
insulation and pipes, if installed. Check and clean on demand and always
minimum twice a year.
2
Saving- and comfort
functions
Test of CO2 sensor, humidity sensor, motion sensor, pressure transmitters
for air capacity control, extended operation via button, cooling recovery, free
cooling
1
Fire alarm Test of thermostats, smoke detectors and fire detection systems
1
Battery in controller Change the battery on demand by alarm in the display and always change
the battery as a minimum every 5 years.
1
Remote control Test of Communications.
1
output | 11