Geniox user manual

Table Of Contents
Instructions for machinery where these are regularly to be transported |
45
O Instructions for machinery where these are regularly to be transported
The subject in the Machinery Directive about machinery that are regularly to be transported does not exist for the Gen-
iox air handling units, because those units are specially made for one intended application.
P The operating method to be followed in the event of breakdown. Safe restart.
Use the below mentioned procedure in the event of breakdown or blockage:
Switch off the power and lock the automatic circuit breaker by padlocks in the off position.
Remove the reason for breakdown or blockage.
Follow the start-up procedure described in chapter J.
Q Adjustment and maintenance operations
Must be performed by skilled technicians.
In connection with demands for compensation, Systemair must have full and unhindered access to all relevant reporting
on service, repair, modification and use since the unit was transferred from Systemair to a transport company at the
Systemair factory. It is a condition for compensation that maintenance outlined on the following pages has as a mini-
mum been performed.
Q.1 Shutdown of the unit to a safe state
Switch the unit to OFF on the Systemair Control Panel. See the - Operator’s Guide if the unit was delivered with control
system from Systemair. Switch off the automatic disconnecting device. The automatic disconnecting device are marked
F1 to F4.
Check that the disconnecting device marked F3 is still switched on because the lamps inside the unit, and only those
lamps, are connected to this switch. Switch on the lamps for light during the maintenance activities. Be aware that F3
also supplies rotary heat exchanger and the Access control system so if the lamps are on, the rotary heat exchanger
and the Access control system are also supplied.
Use the start-up procedure described in chapter J, when the maintenance activities are completed.
Q.2 Unlock and lock the doors by using the key
Use the key to lock the doors. The doors are not locked
automatically by turning the handle to the vertical
position.