Geniox user manual

Table Of Contents
Information about the residual risks |
41
K.4 Risk caused by maintenance and cleaning of dampers
Hazards/dangerous area:
Are between the damper blades and the system of bars and links between motor and damper blades.
Dangerous incident:
Crushing of fingers.
Claim for reduction of danger:
Risk only exists during maintenance and cleaning. This task must be done by skilled technicians that are aware of this
risk.
K.5 Risk caused by maintenance and cleaning of attenuators
Hazards/dangerous area:
High concentration of dust on the surface of the baffles might be harmful to the health.
Dangerous incident:
To breathe in particles that is harmful to the health.
Claim for reduction of danger:
Risk only exists during maintenance and cleaning. This takes place at least one time every year. Use of particulate
respirator is described in this manual. Particulate respirator maintenance free including foam face-seal and adjust-
able pre-threaded headbands (same particulate respirator as recommended for change of filters).
K.6 Risks in connection to filters
K.6.1 Risk caused by missing change of filter
Hazards/dangerous area:
Missing change of filters and missing maintenance decrease the capacity and final consequence will be breakdown.
Dangerous incident:
By extensive lack of filter change and maintenance the machine can break down.
Claim for reduction of danger:
In the manual is the method and schedule for change of filters and maintenance specified.
If the filter is subject to heavier loads, the inspection interval must be shortened accordingly to prevent premature
tearing.
K.6.2 Risk caused by filter change
Hazards/dangerous area:
Filter panels and filter bags
Dangerous incident:
To breathe in particles that are harmful to the health when changing the filter.
Claim for reduction of danger:
Use of particulate respirator maintenance free including foam face-seal and adjustable pre-threaded headbands
(same particulate respirator as recommended for cleaning of attenuators.
K.7 Risks in connection to fans
K.7.1 Risk caused by permanent magnet motor
Hazards/dangerous area:
Rotation of the shaft generates electricity. This danger is always visualized by a yellow warning label on the inspec-
tion door where permanent magnet motors are installed.
output | 11